FlexMax FM100 AFCI Installation

900-0253-01-00 Rev A
55
Troubleshooting
IMPORTANT:
Check the OutBack customer and user forum at www.outbackpower.com/forum/ for more
FLEXmax 100 information.
General Troubleshooting
An OutBack MATE3s system display may be required for certain troubleshooting steps in Table 7.
Table 7 Troubleshooting
Symptom Remedy
Unit does not power up
upon initial connection
(no LED indicators or
system display
operation).
Check the battery connection and polarity. Reverse polarity or an improper
connection will cause power-up issues.
Check the battery circuit breaker or device. Ensure all items are sized appropriately.
Check the battery voltage at the FLEXmax 100 terminals. A battery voltage below
15 Vdc may not power up the charge controller. A poor connection may not allow
sufficient voltage to reach the charge controller.
Rapid shutdown condition. The system display
Fault Input Active
message
will show
Y
(see page 38). This is not a controller error but a deliberate action.
See pages 18, and 24, and 58 for more information. Resetting this condition
requires resetting the external rapid shutdown device.
Upper limits: 24-volt system = 275 Vdc, 36-volt system = 283 Vdc,
48-volt system = 290 Vdc. See page 68 for more information.
IMPORTANT:
The FLEXmax 100 will not function unless jumper J5, the OutBack RSI, or a similar
normally-closed device is installed on the rapid shutdown terminals. Initial power-up
will result in a rapid shutdown signal. See page 24.
Unit powers up but
does not operate.
PV voltage is present
but drops to a few
volts when connected.
Check PV wiring. This will occur if the PV array wiring polarity is reversed.
The heatsink may grow warm after a short time due to internal current flow.
Unit not operating;
unit had worked
normally before.
This behavior is normal in cases of low light. Unit may be in “Sleep”, “Snooze”,
or “Wakeup” modes. Confirm conditions and behavior using Table 4 on page 34.
Battery temperature fault. Check temperature (see system display literature).
If the RTS reads in excess of 50°C, it indicates a battery too hot to safely operate.
Rapid shutdown condition. The system display
Fault Input Active
message
will show
Y
(see page 38). This is not a controller error but a deliberate action.
See pages 18, and 24, and 58 for more information. Resetting this condition
requires resetting the external rapid shutdown device.
Module-level electronics may be interfering with the system (see page 26).
Consult the literature or manufacturer of any third-party products.