FlexMax FM100 AFCI Installation

Specifications
900-0253-01-00 Rev A
63
Temperature Range and Derating
In standard installations, the FLEXmax 100 can operate at its full 100-amp capacity at ambient
temperatures up to 25°C (77°F). Above this temperature, its output is derated as described below.
The values depicted in Figure 53 are examples for a system with a PV input of 220 Vdc. Lower input
voltage will improve the controller’s thermal performance.
For a nominal 24-volt battery system:
At 60°C (140°F), the output is derated to a maximum of 46 Adc. The controller is not rated for operation above
this temperature.
For a nominal 48-volt battery system:
At 60°C (140°F), the output is derated to a maximum of 50 Adc. The controller is not rated for operation above
this temperature.
Figure 53 Temperature Derating
NOTE:
The temperatures shown here are the external ambient temperatures that usually
accompany derating conditions. For the actual internal temperature readings that result in
derating, see page 38.
DEGREES
24 Vdc
AMPERES
50A
46A
25°C
48 Vdc