FlexMax FM100 AFCI Installation

900-0253-01-00 Rev A
9
Installation
Standards and Requirements
Installations must comply with all national and local electrical codes. Professional installation is
recommended. See page 7 for qualifications of installers.
A FLEXmax 100 charge controller operating in unventilated or in other conditions above an ambient
temperature of 25°C (77°F) will have a derated power output. See page 63 for more information.
If damaged or malfunctioning, the FLEXmax 100 should only be serviced by qualified personnel.
Please contact the local renewable energy dealer/installer for assistance.
Dimensions and Clearances
Figure 2 FLEXmax 100 Dimensions
Clearance requirements (minimum)
Above the ground or floor surface: 36” (91.4 cm)
Above and below the controller: 6“ (15.2 cm)
Right and left sides: 1” (2.5 cm)
~ This includes clearance for multiple controllers installed next to each other.
Wiring
compartment
height
4.4” (11.2 cm)
Side Plugs: 3.27” (8.3 cm)
De
p
th 6.0”
(
15.2 cm
)
Height
18.6”
(47.2 cm)
Height
with fan
23.0”
(58.4 cm)
Bottom Plugs: 3.3” (8.4 cm)
W
idth 8.8”
(
22.4 cm
)
Wiring compartment opening width
6.9
(17.6 cm)
These openings are for 1” conduit
(1” actual diameter)