Outback FM60 User Manual

Installation
900-0009-01-00 Rev D 13
Wiring Compartment
WARNING: Shock Hazard
Make sure all DC circuit breakers are OFF (open) BEFORE making any wiring connections.
Use a DVM to check for voltage on all wires.
The PV– (negative) and BAT– (negative) terminals are connected internally. Only one negative
wire may be needed to connect to the (–) wire lugs if the PV– and BAT– conductors are bonded
at the negative bus bar.
See Figure 6, Figure 7, and Figure 8 for sample wiring diagrams.
Figure 5 Wiring Compartment
CAUTION: Equipment Damage
Each FLEXmax requires its own PV array. DO NOT PARALLEL FLEXmax PV+ and PV-
TERMINALS ON THE SAME ARRAY!
An optional battery Remote Temperature Sensor (RTS) is recommended for accurate
battery charging.
o
Only one RTS is needed for multiple OutBack inverter/chargers and charge controller units when the
system includes an OutBack HUB and a system display.
o
When one RTS is used, it must be connected to the component plugged into
P
ORT
1
of the HUB.
Chassis/Equipment
Ground Lug
o Use up to 35 mm
2
(#2 AWG) wire
o Torque to 4 Nm (35 in-lb)
MATE/HUB
RJ45 port
Battery Remote
Temp Sensor
(RTS) RJ11 port
Auxiliary Output
(
A
UX) Terminals
W
ire terminals
Screw holes for mounting
the charge controller
PV+
PV– BAT–
BAT+