Outback FM60 User Manual

Operation
900-0009-01-00 Rev D 23
Table 1 Battery Voltage and Charge Timer
Battery Voltage ChgT (Charge Timer) Activity/Display
12.4 V, 24.8 V, 37.2 V, 49.6 V, or 62.0 V,
and less than the Absorbing voltage
No change.
<12.4 V, 24.8 V, 37.2 V, 49.6 V, or 62.0 V
For every minute elapsed, 1 minute is subtracted
from the timer.
<12.0 V, 24.0 V, 36.0 V, 48.0 V, or 60.0 V
For every minute elapsed, 2 minutes is subtracted
from the timer.
< 11.6 V, 23.2 V, 34.8 V, 46.6 V, or 58.0 V
For every minute elapsed, 4 minutes is subtracted
from the timer.
Auto Start (Auto ReStart)
This setting allows the user to choose between continuous MPP tracking or occasional restarts
of the sweeping process. A restart means the controller abandons the existing MPP and
“re-sweeps”, or begins gathering new power point data. See page 55 for more information.
o
Mode 1: Once every 1.5 hours in the Bulk charging stage
o
Mode 2: Once every 1.5 hours in the Bulk, Absorbing and Float recharging stages
o
Mode 0: Auto ReStart is disabled completely. It will continously track the maximum power point
without starting over.
NOTE: If enabled, AutoStart also occurs during the MPPT EQ cycle. See page 25.
BatTmpErr
The battery temperature sensor is shorted or damaged. Charging will not be temperature
compensated. (The cooling fan will continuously operate.) See RTS compensation on page 53.
BatTooHot
The battery temperature sensor has detected a battery temperature of over 50°C. The
FLEXmax will stop charging the battery and wait for the battery to cool below 50°C.
Charged
There is an external DC source other than PV keeping the battery above the Float voltage set
point (see page 29). The FLEXmax will stop charging because it is not needed. The display
may also appear when the cycle is transitioning from Absorbing (upper target voltage) to
Floating (lower voltage).
EQ
The charger is in a cycle of equalization. (See page 45.) This is the time elapsed in hours and
minutes since the BATTERY EQUALIZE VOLTS set point was met.
If this set point is not maintained, the controller will revert back to MPPT EQ. (See page 25.)
The EQ timer will pause until the batteries are regulated at the BATTERY EQUALIZE VOLTS
set point again. The paused time can be viewed in End-of-day Summary (see page 20).
EQ Done
Once the set EQ time (between 1 and 7 hours) has successfully completed, the FLEXmax will
transition to Float stage. EQ Done will be displayed either until a button is pressed or the next
morning’s wakeup. The FLEXmax will transition to Float stage at the end of the completed
equalization cycle.