Outback FM60 User Manual

Operation
900-0009-01-00 Rev D 41
Figure 26 Setting the Diversion:Solid St Mode (Part 2)
To change the set points for Diversion:Solid St:
1. Press <SET> to advance to the set point screens <VOLT>
and <TIME>.
2. Press <TIME> to advance to the Time screen. This allows the
user to adjust the minimum time the A
UX output is active after
the battery voltage falls below the hysteresis voltage.
3. Press <-> or <+> to increase or decrease the Hold time values.
4. Press <DLY+> to increase the Delay time.
5. Press <BACK> to return to the Diversion:Solid St TIME and
VOLT screen.
6. Press <VOLT> to move into the Relative Volts screen.
7. Press <-> or <+> to increase or decrease the values.
8. Press <HYST> to select the hysteresis value.
9. Press <BACK> to return to the Diversion:Solid St Time and
Volt screen.
10. From the Diversion:Solid St screen, press <EXIT> to return to
the AUX MODE screen.
AUX MODE
Diversion:Solid St
Output: Off Off
EXIT NEXT SET MODE
AUX MODE
Diversion:Solid St
EXIT TIME VOLT
Absorb--Float--EQ
Relative Volts
0.0 00.2
BACK - + HYST
Hold Delay
01.0 Time 00
Seconds
BACK - + DLY+
Hold time shows how long the
A
UX mode
stays active after the battery voltage has
fallen below the HYST
(Hysteresis) set
point. The user can adjust the Hold time
from 0.1 to 25 seconds.
The Delay Time shows how long the
battery voltage must be above the
Relative Volts before the A
UX mode is
activated. It can be adjusted from 0 to
24 seconds, but is rarely required.
Use this screen to establish the set points for
starting and ending the A
UX mode relative
to the Absorb, Float, and EQ voltages.
The <HYST> (hysteresis) set point establishes
when the AUX mode becomes inactive after the
battery voltage falls below the Relative Volts
voltage minus the HYST value.
Continued from previous pageā€¦
To Exit:
o Press <EXIT> once to
return to the main menu.
o Press <EXIT> twice to
return to the status screen.