Low Battery Disconnect (AUX Mode)
This mode disconnects “auxiliary” loads from the batteries in the event of low voltage. These
are separate from the usual loads. Auxiliary loads are controlled by the A
UX output, usually by
a larger relay. When the battery voltage falls below DISCONNECT VOLTS setting, A
UX loads
are disconnected. When it rises above RE-CONNECT VOLTS, they will be reconnected.
Any loads not controlled this way, such as an inverter, may continue discharging the battery.
Figure 28 Low Battery Disconnect Mode
To set the mode for Low Battery Disconnect in AUX mode:
1. From the main menu, press <> or <> to move the
to the left
of the Aux.
2. Press <GO> to open the AUX MODE screen.
3. Press <NEXT> until the Low Batt Disconnect Mode is displayed
in the AUX MODE screen.
4. Press <MODE> to cycle through the mode set points;
ON, OFF, or AUTO.
o ON activates the A
UX output.
o OFF deactivates the AUX output.
o AUTO controls the output according to the criteria of the
selected A
UX mode.
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
Main Menu
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
AUX MODE
Low Batt Disconnect
Output: Off Off
EXIT NEXT SET MODE
<NEXT> proceeds to the
next AUX MODE screen.
To change the set points for Low Battery Disconnect:
1. Press <SET> to advance to the set point screens <VOLT> and <TIME>.
2. Press <TIME> to advance to the Delay Time Sec screen.
3. Press <> or <+> to increase or decrease the values.
4. Press <BACK> to return to the main Low Batt Disconnect screen.
5. Press <VOLT> to advance to the DISCONNECT VOLTS screen.
6. Press <> or <+> to increase or decrease the values.
7. Press <RECON> to advance to the RE-CONNECT VOLTS screen.
8. Press <> or <+> to increase or decrease the values.
9. Press <DisV> to return to the DISCONNECT VOLTS screen.
10. Press <BACK> to return to the Low Batt Disconnect screen.
AUX MODE
Low Batt Disconnect
Output: Off Off
EXIT NEXT SET MODE
AUX MODE
Low Batt Disconnect
EXIT TIME VOLT
RE-CONNECT VOLTS
> 14.4
BACK - + DisV
DISCONNECT VOLTS
< 13.6
BACK - + ReCon
This is the time the FLEXmax waits before either
activating or deactivating the AUX mode when either
the disconnect or reconnect voltages are reached.
When the low voltage occurs, the timer shows the
seconds remaining before disconnecting.
Delay Time Sec
01 Timer
001
To Exit:
o Press <EXIT>
once to return to
the main menu.
o Press <EXIT>
twice to return to
the status screen.