900-0167-01-00 Rev B 67
Figure 22 Temperature Derating
Regulatory Specifications
Listings
This product carries a listing report by ETL. It is listed to the following standards:
UL 1741— Inverters, Converters, Controllers and Interconnection System Equipment for Use With
Distributed Energy Resources (2nd Edition, 1/28/2010)
CSA C22.2 — General Use Power Supplies, No. 107.1-01 Issue: 2001/09/01 Ed:3 (R2006)
Compliance
This product complies with the following standards:
UL 1778 — Uninterruptible Power Systems, Annex FF (normative): Backfeed Protection Test
RoHS: per directive 2011/65/EU
Specification Compliance
Inverters intended for grid-interactive use in the United States and Canada must comply with the
established standards of UL 1741 and IEEE 1547 and 1547.1. These standards provide regulation for
acceptable output voltage ranges, acceptable output frequency, total harmonic distortion (THD) and
anti-islanding performance when the inverter is exporting power to a utility source.
The OutBack grid-interactive models are tested using the procedures listed in IEEE 1547.1 to the
standards listed in both UL 1741 and IEEE 1547. The following specifications have been validated
4000
1000
3000
2000
10°C
50°F
20°C
68°F
30°C
86°F
40°C
104°F
50°C
122°F
0
Output Watts
25°C
77°F
2625
3500
1500
2500
2700
VFXR3648A VFXR3524A
VFXR2812A
FXR3048A
FXR2524A FXR2012A
2100
2250
1875
1500