Table 23 FXR Settings for 12-Volt Models
Field Item Default Minimum Maximum
(Load Shed) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode Master
Master, Slave, L2 Phase Master, B Phase Master,
C Phase Master
Power Save
Ranking
Mode = Master: Master Power Save Level
0 0 10
Mode = Slave: Slave Power Save Level
1 1 10
Grid-Tie Sell
Offset Enable Y Y or N
Sell Voltage
13.0 Vdc 11.0 Vdc 16.0 Vdc
Calibrate
AC Input Voltage
X
0 Vac –7 Vac 7 Vac
AC Output Voltage X
0 Vac –7 Vac 7 Vac
Battery Voltage X
0.0 Vdc –0.2 Vdc 0.2 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency X
60 Hz 50 Hz, 60 Hz
Stage 1 Voltage Trip
15
Over Voltage Clearance Time X
1.0 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X
132 Vac 120 Vac 150 Vac
Under Voltage Clearance Time X
2.0 seconds 0.12 seconds 5.0 seconds
Under Voltage Trip X
106 Vac 80 Vac 120 Vac
Stage 2 Voltage Trip
15
Over Voltage Clearance Time X
0.16 seconds 0.12 seconds 5.0 seconds
Over Voltage Trip X
144 vac 120 Vac 150 Vac
Under Voltage Clearance Time X
0.16 seconds 0.12 seconds 5.0 seconds
Under Voltage Trip X
60 Vac 60 Vac 120 vac
Frequency Trip
15
Over Frequency Clearance Time X
0.16 seconds 0.12 seconds 5.0 seconds
Over
Frequency Trip
60-Hz system
X
60.5 Hz 60.2 Hz 65.0 Hz
50-Hz system 50.5 Hz 50.2 Hz 55.0 Hz
Under Frequency Clearance Time X
0.16 seconds 0.12 seconds 5.0 seconds
Under
Frequency Trip
60-Hz system
X
59.3 Hz 55.0 Hz 59.8 Hz
50-Hz system 49.3 Hz 45.0 Hz 49.8 Hz
Mains Loss
15
Clearance Time X
2.0 seconds 1.0 seconds 25.0 seconds
Reconnect Delay X
300 seconds 2 seconds 302 seconds
Multi-Phase Coordination
Coordin. AC Connect/Disconn. N Y or N
Sell Current Limit
Maximum Sell Current X
This selection inoperative in 12-volt models
Model Select
X
Vented Vented or Sealed
15
The grid-interactive function is not available in 12-volt models. Adjusting these items will not affect operation.