Installation Guide
Installation
28
900-0160-01-01 Rev B
Figure 16 DC Cable Hardware (Radian inverter)
If the battery cables are connected directly to the Radian inverter, the hardware should be arranged as shown in
image
A
. The inverter’s battery terminal is a threaded hole which accepts a hex bolt (provided). The battery cable
lug must have a 0.79 cm (5/16") diameter hole.
If the inverter is installed with the GS Load Center (GSLC), follow GSLC instructions for hardware installation.
The hardware should be arranged according to the appropriate image below
.
GSLC models used with the GS8048A inverter are equipped with a DC positive (+) plate. The plate accepts an M8
hex bolt and nut. See image
B
.
GSLC models used with the GS4048A inverter do not use the DC positive plate. The cable lugs are connected to
the DC disconnect, which uses a threaded M8 stud. See image
C
.
All GSLC models connect the battery negative cables to the shunt, which is threaded for ⅜” bolts. See image
D
.