Radian E-Series SPECIFICATIONS 06/2017
7.0kVA 7.0kW 7.0kVA
5.95kW
Power Rating Notes
Inverters that specify power in VA but do not use the
unity standard Power Factor (PF) could have misleading
power specications. Volt-Amps (VA) is a total inverter
output, while Watts (W) represent the power consumed by the
electrical loads. PF, which varies by types of loads, is the ratio
of W to VA, and the dierence between the two is power in the
circuit that does no useful work. At 1.0PF (unity), all power is
used. This is the industry-standard used by OutBack Power.
Radian GS7048E Power Factor Chart
Power Factor
1.0
0.75
0.5
0.25
0.0
Industry-Standard Non-Industry Standard
0.85
Radian GS7048E Power Rating Chart
Power (VA)
20000
15000
10000
5000
0
100ms 5 sec 30 min continuous
Instantaneous Power Rating
Most stringent, massive load start GS7048E: 16300VA
Surge Power Rating
Less stringent load start GS7048E: 11500VA
Peak Power Rating
Frequent “heavy duty” load requirements GS7048E: 7900VA
Continuous Power Rating
Sustained “real world” load requirements GS7048E: 7000VA
16300VA
11500VA
7900VA
7000VA
Models:
GS7048E GS3548E
Instantaneous Power (100ms)
16300VA 8200VA
Surge Power (5 sec)
11500VA 5800VA
Peak Power (30 min)
7900VA 4000VA
Continuous Power Rating (@ 25°C)
7000VA 3500VA
Nominal DC Input Voltage
48VDC 48VDC
AC Output Voltage (selectable)
230VAC (210-250VAC) 230VAC (210-250VAC)
AC Output Frequency (selectable)
50Hz (60Hz) 50Hz (60Hz)
Continuous AC Output Current (@ 25°C)
30AAC 15.2AAC
Idle Power
Invert mode, no load: 34W Search: 10W Invert mode, no load: 34W Search: 10W
Typical Eciency
92% 92%
Peak Eciency
96% 96%
Total Harmonic Distortion
Typical: <2% Maximum: <5% Typical: <2% Maximum: <5%
Output Voltage Regulation
±2% ±2%
AC Input Voltage Range (MATE3 Adjustable)
L-N: 170 to 290VAC L-N: 170 to 290VAC
AC Input Frequency Range
@ 50Hz: 45 to 55Hz @ 60Hz: 54 to 66Hz @ 50Hz: 45 to 55Hz @ 60Hz: 54 to 66Hz
Grid-Interactive Voltage Range
L-N: 208 to 252VAC L-N: 208 to 252VAC
Grid-Interactive Frequency Range
@ 50Hz: 47 to 51Hz @ 60Hz: 57 to 61Hz @ 50Hz: 47 to 51Hz @ 60Hz: 57 to 61Hz
Maximum AC Input Current
50AAC 50AAC
Maximum Utility Interactive Current
30A 15A
Continuous Battery Charge Output
100ADC 50ADC
Advanced Battery Charging
Flooded, gel, AGM, lithium-ion and ow chemistry Flooded, gel, AGM, lithium-ion and ow chemistry
DC Input Voltage Range
40 to 64VDC 40 to 64VDC
Accessory Ports
Remote temperature sensor (included), MATE3 and HUB communications Remote temperature sensor (included), MATE3 and HUB communications
Warranty
Standard 5 year, extended 10 year available Standard 5 year, extended 10 year available
Weight (lb/kg)
Unit: 125 / 56.7 Shipping: 140 / 63.5 Unit: 82 / 37.2 Shipping: 94 / 42.6
Dimensions H x W x L (in/cm)
Unit: 28 x 16 x 8.7 / 71.1 x 40.6 x 22.1 Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8 Unit: 28 x 16 x 8.7 / 71.1 x 40.6 x 22.1 Shipping: 34.5 x 21 x 14.5 / 87.6 x 53.3 x 36.8
Temperature Range
Rated: -20 to 50°C Maximum: -40 to 60°C Rated: -20 to 50°C Maximum: -40 to 60°C
Listings/Certications
IEC 62477-1, AS4777.2, AS477.3, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3, AS3100, CE,
RoHS compliant per directive 2011/65/EU
IEC 62477-1, AS4777.2, AS477.3, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3, AS3100, CE,
RoHS compliant per directive 2011/65/EU
Peak Eciency Rating
Highest eciency rating achievable GS7048E: 96%
Typical Eciency Rating
Real world eciency with variable loads GS7048E: 92%
Radian GS7048E Eciency Rating Chart
Eciency
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
2kVA 4kVA 6kVA 8kVA
96% (Peak)
92% (Typical)
INVERTING SELLING