Figure 31 Parallel Wiring with GSLC
1. Ground wiring is not shown for reasons of simplicity. Regardless, this system must be connected to a grounded, permanent
wiring system. See page 25.
2. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically
common. If an external neutral bus exists (as shown in the GSLC), not all of the Radian neutral connections need to be made.
In this example, only the Grid neutral terminal on each inverter is connected.
3. The bypass assembly in each GSLC cannot be used with multiple inverters and is not depicted here. External bypass
assemblies are available from other manufacturers. See page 15.
NOTES: