Installation Manual

66
HBX-Drop Grid Set Point
HBX-Drop Grid Delay
ADV/MATE/HBX---------------------
hbx-drop 26.0 vdc
grid setpoint
DOWN UP INC DEC
ADV/MATE/HBX---------------------
hbx-drop 01.0 hrs
grid delay
DOWN UP INC DEC
issetpointshowsthevoltage—26.0VDC
isthedefaultfora24Vsystem—atwhichthe
FXwillDROPitsACinputsource.ebattery
voltage must remain above this voltage for the
amountoftimesetbyHBX-DROPGRIDDELAY
(nextscreen)foraDROPtobeissued.Pressthe
<DOWN> so key to proceed.
issetpointistheamountoftime—01.0hrsin
thiscase—batteryvoltagemustremainabovethe
HBX-DROPGRIDSETPOINT(seeprevious
screen)beforeaDROPcommandissent.Itcan
rangefrom00.1hrsto24.0hrsin0.1hourincre-
ments. ese increments are adjusted using the
<INC> and <DEC> so keys. Press the <DOWN>
so key to proceed.
Withthisscreen,HBXModecanbeenabledor
disabled. Pressing <CHANGE> allows you to
changethecurrentmodeinthenextscreen.
AC Input Control
ADV/MATE/HBX---------------------
ac input USE
control
DOWN UP CHANGE
NOTE:BeforeenablingHBXMode,makesurethe
FXisinDROPmodebypressingthe<DROP>
sokey.escreenwillindicateDROPmode,
allowingtheMATEtoresettheHBXvalues.
ADV/MATE/HBX---------------------
ac input USE
control
DROP USE HBX DONE