Outback FX-R Series Operator Manual

Specifications
900-0167-01-01 Rev A 73
Table 23 FXR Menu Items for 48-Volt Models
Field Item Default Minimum Maximum
Auxiliary Output
Aux Control
Auto
Off, Auto or On
Aux Mode
Cool Fan
Load Shed, Gen Alert, Fault, Vent Fan,
Cool Fan, DC Divert, GT Limits,
Source Status, AC Divert
(Load Shed) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt <
44.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt <
44.0 Vdc 40.0 Vdc 72.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode
Master
Master, Slave, L2 Phase Master, B Phase
Master, C Phase Master
Power Save
Ranking
Mode =
Ma
ster:
Master Power Save Level
0 0 10
Mode = Slave: Slave Power Save Level
1 1 10
Grid-Tie Sell
Offset Enable
Y Y or N
Sell Voltage
52.0 Vdc 44.0 Vdc 64.0 Vdc
Calibrate
AC Input Voltage X
0 Vac
–7 Vac
7 Vac
AC Output Voltage X
0 Vac –7 Vac 7 Vac
Battery Voltage X
0.0 Vdc –0.8 Vdc 0.8 Vdc
Grid Interface Protection Menu
Operating
Frequency
Operating Frequency X
60 Hz 50 Hz, 60 Hz
Mains Loss
Clearance Time X
2.0 seconds 1.0 seconds 25.0 seconds
Reconnect Delay X
300 seconds 2 seconds 302 seconds
Multi-Phase Coord.
Coordinated AC Connect/Disconnect
N Y or N Y
Sell Current Limit
Maximum Sell
Current
FXR3048A
X
24 Aac 5 Aac 24 Aac
VFXR3648A
24 Aac 5 Aac 30 Aac
Grid Support
Defaults shown are
for IEEE 1547
setting
Grid Support Functions X
N/A
Start Ramp, Freq/Watt, Ramp Rates,
Volt/Watt, Fixed PF, Volt/VAr
Regulatory Specification X
IEEE 1547
IEEE 1547, HECO Rule 14, AS4777,
ABNT 16149, CA Rule 21
Low/High
Voltage Ride-
Through
OV2
Volts
X
144 Vac 120 Vac 144 Vac
Mode
Cont.
Con
t., Mand., Mom., Perm., Cease
Trip
0.16 seconds 0.12 seconds 5.00 seconds
OV1
Volts
X
132 Vac 120 Vac 140 Vac
Mode
Cont.
Con
t., Mand., Mom., Perm., Cease
Trip
1 second 1 second 50 seconds
UV1
Volts
X
106 Vac 60 Vac 120 Vac
Mode
Cont.
Con
t., Mand., Mom., Perm., Cease
Trip
2 seconds 1 second 50 seconds