The
Support
mode is intended for systems that use the utility grid or a generator. In some
cases the amount of current available from the source is limited due to size, wiring, or other
reasons. If large loads are required, the FXR inverter augments (supports) the AC source.
The inverter uses battery power and additional sources to ensure that the loads receive the
power they demand.
In a MATE3-class system display, the
Grid Input AC Limit
dictates the maximum AC draw for
the Grid input. The
Gen Input AC Limit
sets the maximum draw for the Gen input. The
Support
function takes effect if the AC demand on either input exceeds the
AC Limit
setting.
BENEFITS
:
Large inverter loads can be powered while staying connected to the AC input, even if the input is
limited. The added battery power prevents overload of the input source, but the batteries are not in
constant use.
The FXR inverter will offset the loads with excess renewable energy if it is available from the
batteries. See page 37 for more information on the
Offset
function.
NOTES
:
IMPORTANT:
The inverter will draw energy from the batteries when the loads exceed the appropriate
AC Limit
. With sustained loads and no other DC source, the batteries may discharge to the
Low Battery Cut-Out
point. The inverter will shut down with a
Low Battery
error. (See
pages 22 and 52.) To prevent the loss of power, load use should be planned accordingly.
IMPORT
ANT:
A “noisy” or irregular AC source may prevent
Support
from working normally. The inverter
will transfer the power, but will not support the source, charge the batteries, or interact with
the current in any other way. This problem is more common with generators smaller than
the wattage of the inverter.
Because the inverter limits the current draw from the AC source, it will reduce the charge rate as
necessa
ry to support the loads. If the loads equal the appropriate
AC Limit
setting, the ch
arge rate
will be zero.
If the AC loads
exceed
the
AC Limit
setting, the Support function is activated. Instead of charging,
the inverter
will take power from the batteries and use it to support the incoming
AC current.