Outback FX-R Series Operator Manual

Operation
900-0167-01-01 Rev A
35
Figure 7 Repeated Charging (3
rd
, 4
th
, and 5
th
Cycles)
Prior to the beginning of Cycle 3, the AC source was lost. The battery voltage decreased below
the level of the
Re-
Bulk
set point. Whenever this occurs, the Absorption time
r resets to its
maximum amount.
In Figure 7, Cycle 3 begins when the AC source is restored again. The charger begins a new cycle
by entering B
ulk stage. When it enters Absorption, the timer runs until it is interrupted by a lo
ss of
AC power.
Following Cycle 3, the voltage does not decrease below
Re-Bulk
. The Absorption timer retains the
remai
ning time from Cycl
e 3.
Cycle 4 begins when the AC source is restored again. The charger enters Bulk stage and proceeds
to Absorption
. This stage does not last for the full duration of the
Absorb Time
se
tting. The timer
use
s up the remaining time from Cycle 3. Absorption ends when the timer expi
res.
In this examp
le, the duration was also longer than the
Float Time
setting. Because the Float ti
mer
bega
n running near the beginning of Cycle 3 and also Cycle 4 (when the batteries exceeded
the
Float Voltag
e
setting), the
Float Time
has also expired. The charger does no
t enter Refloat or Float
and go
es Sile
nt.
Duri
ng the Silent period, AC is lost again. The battery voltage decreases until it reaches the
Re-Bulk
set point, prompting a new charge cycle. The Absorption timer resets to its
maximum amount.
When Cycle 5 begins, the charger proceeds through the Bulk stage and then the Absorption stage.
At the end of Cycle 5, the
Float Time
h
as expired, so the charge
r goes Silent.
Cycle 4
Cycle 3
Absorption
Set Poin
t
Float
Set Poin
t
Re-Bul
k
Set Point
AC Loss
Absorption
timer resets
Absorption
timer runs
(part)
Inverter waiting to charge when AC restored;
a new set point is in use
Inverter now charging to a new
set point
Inverter has reached the charging
set point
Inverter completed charging; the previous set point
is no longer in use
Inverter waiting to charge when AC restored;
the previous set point is still in use
AC Loss
AC Loss
Bulk
Abs.
Silent
Bulk
Absorption
Silent
Bulk
Absorption
Cycle 5
Absorption
timer
resets
Absorption
timer runs
(remaining time)
Absorption
timer runs
(complete)