Troubleshooting
Basic Troubleshooting
Table 6 is organized in order of common symptoms, with a series of possible causes. Each
shows possible troubleshooting remedies, including system display checks where appropriate.
These instructions are for use by qualified personnel who meet all local and governmental code
requirements for licensing and training for the installation of electrical power systems with AC
and DC voltage up to 600 volts.
Figure 12 AC Test Points
WAR
NING: Shock Hazard
During an error shutdown, the inverter’s output terminals are not live. However, if
the inverter recovers from a shutdown, the terminals will become live without notice.
Several error shutdowns can be recovered automatically, including
Low Battery V
,
High Battery V
, and
Over Temperature
. See page 52.
NOTE:
In Table 6, “System display only” usually indicates that a MATE3-class device is
required to perform the step. It cannot be performed without the system display.
Table 6 Troubleshooting
Symptom Possible Cause Possible Remedy
No AC output
(will not invert).
No DC voltage. Use a DC voltmeter to check the voltage directly on the DC
terminals. If not present, the problem is external. If present,
the inverter could be dama
g
ed.
I
NVERTER
O
N
/
O
FF
jumper
missing.
See the
Installation Manua
l for the location of the jumper.
Confirm the jumper is present. If missing, replace the jumper.
Or follow the manual instructions to install an external switch.
Unit defaulted off
(No system display; initial
install;
I
NVERTER
O
N
/O
FF
j
um
p
er confirmed
p
resent
)
.
The FXR inverter is given an initial
Of
f
command in the
factory. With DC present, use narrow pliers to remove the
jumper from its pins. Once removed, install it again. This is
the e
q
uivalent of “
j
i
gg
lin
g
the switch.”
Inverter set to
Of
f
.
System display only:
Set to
On
with
INVERTER
hot key.
NOTE
: The
O
N
/O
FF
jumper must be installed.
Inverter set to
Search
mode.
System display only:
If constant power is required, set to
On
with the
INVERTER
hot key. (If this setting was intentional,
then no action is re
q
uired.
)
In troubleshooting, AC
voltages can be measured
at the attachment screw for
each AC conductor.