To calculate the chargers and settings:
1. Look up the values for A, B, and C.
A = the battery bank’s maximum charge current (in Adc) from the battery manufacturer.
B = the maximum DC output of the appropriate inverter model. This is taken from Table 20.
C = the maximum AC input of the appropriate inverter model. This is taken from Table 20.
2. Select a value for D to be used in the following calculation.
D = the Charger AC Limit setting. This value must be 12 or higher. (See page 63.) A higher value
uses fewer chargers and turns off all others. A lower value, or 12, leaves more chargers on.
3. Perform the following calculation.
A
(C) ÷ D = E
B
E = the number of chargers to use. This number should be rounded down in all cases.
4. Adjust the master inverter’s Charger AC Limit setting to equal D.
5. Turn off the chargers for all inverters that exceed E. In a system stacked on the HUB
comm
unications manager, chargers on higher-numbered ports should be turned off first. Charge
rs
should be turned off by setting the Charger Control menu item to Off. (See the menu tables
beginning on page 66 to locate this command in the menu structure.)
Table 20 Charge Currents for Calculations
Model Maximum DC Output (sent to battery) Maximum AC Input (used from source)
FXR2012A 100 Adc 14 Aac
VFXR2812A 125 Adc 18 Aac
FXR2524A 55 Adc 14 Aac
VFXR3524A 82 Adc 20 Aac
FXR3048A 35 Adc 14 Aac
VFXR3648A 45 Adc 20 Aac
Firmware Revision
This manual applies to inverter models with Revision 001.006.063 or higher.
Updates to the inverter’s firmware are periodically available. These can be downloaded from
the OutBack website
www.outbackpower.com
.
Default Settings and Ranges
NOTES
:
Certain items are retained at the present setting even when the inverter is reset to
factory defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of
these items is changed in a mode menu, all menu items with this set point will show the
same change.
Certain menus are only visible when the installer password is used, particularly the
Grid
Interface Protection
menu. These menus are bordered in the table with a double line of this
style: