Outback FX-R Series Operator Manual

Specifications
66 900-0167-01-01 Rev A
Table 21 FXR Menu Items for 12-Volt Models
Field Item Default Minimum Maximum
INVERTER
Hot Key
Inverter Mode Off On, Off, or Search
CHARGER
Hot Key
Charger Control On On or Off
AC Input
Hot Key
AC Input Mode Use Drop or Use
Search
Sensitivity (see page 24 for increments) 30 0 200
Pulse Length 8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spacing 60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Type Grid Grid or Gen
Charger Control On On or Off
Grid Input AC Limit 60 Aac 5 Aac 60 Aac
Gen Input AC Limit 60 Aac 5 Aac 60 Aac
Charger AC Limit
FXR2012A 12 Aac 0 Aac 14 Aac
VFXR2812A 16 Aac 0 Aac 18 Aac
Grid AC Input
Mode and Limits
Input Mode Support
Generator, Support, UPS, Backup, Mini Grid,
Grid Zero
Voltage Limit
4
Lower 108 Vac 85 Vac 110 Vac
Upper 132 Vac 125 Vac 140 Vac
Transfer Delay
4
1.0 seconds
0.12 seconds 4.0 seconds
Connect Delay
4
0.2 minutes 0.2 minutes 25.0 minutes
If Mini Grid is
selected:
Connect to Grid 12.0 Vdc 11.0 Vdc 16.0 Vdc
(Connect) Delay 10 minutes 2 minutes 200 minutes
If Grid Zero is
selected:
DoD Volts 12.5 Vdc 11.0 Vdc 16.0 Vdc
DoD
Amps
FXR2012A 12 Aac 1 Aac 16 Aac
VFXR2812A 12 Aac 1 Aac 22 Aac
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, UPS, Backup, Mini Grid,
Grid Zero
Voltage Limit
4
Lower 108 Vac 85 Vac 110 Vac
Upper 140 Vac 125 Vac 140 Vac
Transfer Delay
4
1.0 seconds 0.12 seconds 4.0 seconds
Connect Delay
4
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid is
selected:
Connect to Grid 12.0 Vdc 11.0 Vdc 16.0 Vdc
(Connect) Delay 10 minutes 2 minutes 200 minutes
If Grid Zero is
selected:
DoD Volts 12.5 Vdc 11.0 Vdc 16.0 Vdc
DoD
Amps
FXR2012A 12 Aac 1 Aac 16 Aac
VFXR2812A 12 Aac 1 Aac 22 Aac
AC Output
Output Voltage X 120 Vac 100 Vac 130 Vac
Low Battery
Cut-Out Voltage 10.5 Vdc 9.0 Vdc 13.5 Vdc
Cut-In Voltage 12.5 Vdc 10.0 Vdc 14.0 Vdc
Battery Charger
Absorb Voltage 14.4 Vdc 11.0 Vdc 16.0 Vdc
(Absorb) Time 1.0 hours 0.0 hours 24.0 hours
Float Voltage 13.6 Vdc 11.0 Vdc 16.0 Vdc
(Float) Time 1.0 hours 0.0 hours 24/7
Re-Float Voltage 12.5 Vdc 11.0 Vdc 16.0 Vdc
Re-Bulk Voltage 12.0 Vdc 11.0 Vdc 16.0 Vdc
Battery Equalize
Equalize Voltage 14.6 Vdc 11.0 Vdc 17.0 Vdc
(Equalize) Time 1.0 hours 0.0 hours 24.0 hours
Auxiliary Output
Aux Control Auto
Off, Auto or On
Aux Mode Cool Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
4
These items are not displayed when Grid Zero mode is in use.