72 900-0167-01-01 Rev A
Table 23 FXR Menu Items for 48-Volt Models
Field Item Default Minimum Maximum
INVERTER
Hot Key
Inverter Mode Off
On
,
Off
, or
Search
CHARGER
Hot Key
Charger Control On
On
or
Off
AC Input
Hot Key
AC Input Mode Use
Drop
or
Use
Search
Sensitivity (see page 24 for increments) 30 0 200
Pulse Length 8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spacing 60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Type Grid
Grid or Gen
Charger Control On
On
or
Off
Grid Input AC Limit 60 Aac 5 Aac 60 Aac
Gen Input AC Limit 60 Aac 5 Aac 60 Aac
Charger AC Limit
FXR3048A 12 Aac 0 Aac 14 Aac
VFXR3648A 18 Aac 0 Aac 20 Aac
Grid AC Input
Mode and Limits
Input Mode Support
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit
6
Lower 108 Vac 85 Vac 110 Vac
Upper 132 Vac 125 Vac 140 Vac
Transfer Delay
6
1.0 seconds
0.12 seconds 4.0 seconds
Connect Delay
6
0.2 minutes
0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid 48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay 10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts 50.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
FXR3048A 12 Aac 1 Aac 24 Aac
VFXR3648A 12 Aac 1 Aac 30 Aac
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit
6
Lower 108 Vac 85 Vac 110 Vac
Upper 140 Vac 125 Vac 140 Vac
Transfer Delay
6
1.0 seconds
0.12 seconds 4.0 seconds
Connect Delay
6
0.5 minutes
0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid 48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay 10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts 50.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
FXR3048A 12 Aac 1 Aac 24 Aac
VFXR3648A 12 Aac 1 Aac 30 Aac
AC Output
Output Voltage X 120 Vac 100 Vac 130 Vac
Low Battery
Cut-Out Voltage 42.0 Vdc 36.0 Vdc 54.0 Vdc
Cut-In Voltage 50.0 Vdc 40.0 Vdc 56.0 Vdc
Battery Charger
Absorb Voltage 57.6 Vdc 44.0 Vdc 64.0 Vdc
(Absorb) Time 1.0 hours 0.0 hours 24.0 hours
Float Voltage 54.4 Vdc 44.0 Vdc 64.0 Vdc
(Float) Time 1.0 hours 0.0 hours 24/7
Re-Float Voltage 50.0 Vdc 44.0 Vdc 64.0 Vdc
Re-Bulk Voltage 48.0 Vdc 44.0 Vdc 64.0 Vdc
Battery Equalize
Equalize Voltage 58.4 Vdc 44.0 Vdc 68.0 Vdc
(Equalize) Time 1.0 hours 0.0 hours 24.0 hours
6
These items are not displayed when Grid Tied or Grid Zero modes are in use.