Cut Sheet

GB1 GB1
Effective December, 2007
Copyright 2007
800-621-1506
www.o-zgedney.com
Liquidtight & Ground-Tite Connectors
Ground-Tite
®
Grounding Liquidtight Connectors
Type 4Q-L
Straight Connectors
Use:
Secures, grounds and seals liquidtight
flexible metal conduit and terminates
bonding conductor run externally alongside
liquidtight conduit.
Features:
• Positive grounding type
Tapered threaded male hub NPT
• Grounding lug is cast as an integral part
of malleable iron gland nut. Provides high
ground fault withstand capability
• Compact, slim diameter with small turning
radius
• Furnished with locknut and KO sealing ring.
• Liquidtight/Raintight/Oiltight/Concretetight
• UL Listed NEMA Type 4 when installed
into a NPT threaded entry or UL Listed
conduit hub (sizes 1
1
4 and larger require
thread sealant).
• Suitable for use in the following
Hazardous Locations:
Class I, Div. 2 per NEC 501.4(B)
Class I, Zone 2 per NEC 505.15(C)(2)
Class II, Div. 1 per NEC 502.4(A)(1)(e)
Class II, Div. 2 per NEC 502.4(B)(2)
Class III, Div. 1 per NEC 503.3(A)(2)
Class III, Div. 2 per NEC 503.3(B)
Intrinsically Safe per NEC 504.20
• Bonding Wedge Locknuts are recom-
mended in Hazardous Locations. See 101
Series on Page DB8.
• Long ferrule prevents pull-out and tight
bend conduit “pop-out”
• Inspection windows in ferrule to ensure full
engagement
• See Page GC4 for our patented Ferrule
Wrench which makes ferrule installation
easy.
Material/Finish:
Malleable Iron Body and Nut, Zinc
Electroplated. Steel Ferrule, Zinc
Electroplated.
Optional Finish:
Hot Dip or Mechanical Galvanize, add suffix
“G” to catalog number. Contact your local
representative for pricing and availability.
Third Party Certification:
UL Listed: E-24264
CSA Certified: 9795
Insulated
Dimensions in Inches
Throat Turning
Trade Size Catalog Catalog Radius Wire Size
(inches)
Number Number A B C Gland Nut Min. Max.
3
8 (
1
2 KO) 4Q-38L 4Q-38LT
7
8
1
2 1
11
16 1
1
16 14 4
1
2 4Q-50L 4Q-50LT
7
8
1
2 1
7
8 1
3
16 14 4
3
4 4Q-75L 4Q-75LT 1
1
2 2
1
8 1
5
16 14 4
1 4Q-100L 4Q-100LT 1
1
8
5
8 2
3
8 1
7
16 14 4
1
1
4 4Q-125L 4Q-125LT 1
5
16
5
8 2
7
8 1
3
4 6 1/0
1
1
2 4Q-150L 4Q-150LT 1
3
8
5
8 3
1
4 1
7
8 6 1/0
2 4Q-200L 4Q-200LT 1
1
2
5
8 3
3
4 2
3
16 6 1/0
2
1
2 4Q-250L 4Q-250LT 1
15
16 1 4
5
8 2
3
4 1 4/0
3 4Q-300L 4Q-300LT 1
15
16 1
1
8 5
5
16 3
1
16 1 4/0
3
1
2 4Q-350L 4Q-350LT 2
5
8 1
1
8 5
13
16 3
3
8 1 4/0
4 4Q-400L 4Q-400LT 2
1
4 1
1
4 6
1
2 3
5
8 1 4/0
5 4Q-500L• 4Q-500LT• 2
3
16 1
1
8 7
1
2 4
3
16 1 4/0
6 4Q-600L•* 4Q-600LT•* 2
1
2 1
3
8 8
1
2 4
3
4 1 4/0
•UL Listing not applicable
*CSA Certification not applicable
Type 4Q-38L — Type 4Q-200L Type 4Q-250L — Type 4Q-600L
Applicable Third Party Standards:
UL Standard: 467
CSA Standard: C22.2 No. 41
NEMA: FB-1
Federal Spec: W-F-406E
Suggested Specification:
Where liquidtight flexible metal conduit is used,
bonding jumpers shall be provided alongside
such conduit and terminated by malleable iron
connectors provided with lugs cast integrally with
the gland nuts. These connectors shall be
O-Z/Gedney Type 4QL.

Summary of content (3 pages)