User's Manual

P. G. TM0047
4-4
4.4 STATUS OPTION (S)
If it is desired to use the amplifier in a system that has "Fault only" monitoring such as is
provided by the PS200 unit, then the "OK" reports may be disabled by removing the
STATUS jumper.
4.5 TEST (T)
The test jumper location does not have any function in normal system operation. It is
provided for use in FAT testing in the factory by speeding up the rate of OK code
reporting. It should be open for normal operation.
4.6 FAULT CODE (C)
If it is required to change the factory set Fault Code to the operator's custom plan then
follow the following steps:
1. Refer to the jumper field with a block of eight jumpers labelled 0 to 7 in Figures 4-1
and 4-2.
2. The code is programmable in binary with the numbers 0 to 7 representing the
power of 2, i.e., the jumper is 2
3
= 8. When the jumper is on the H side the count is
included. When the jumper is on the L side the count is zero for that binary digit.
3. Before reprogramming check the examples, Figure 4-2, and examine the factory
set code as a starting point.
NOTE: The center pin “C” MUST be jumpered to EITHER the “H” or “L” side for a
correct code to be sent. Do not leave open.