User's Manual

Usage
LEDs
Red / GreenGreenRed
Access deniedAccess permittedDefault
Sounder
The reader sounds 4 rapid beeps when it is powered up or restarted.
If specified, the reader beeps once when a token is presented.
Cable Lengths
PAC door controllers only
Distance from Reader to ControllerCable Gauge
PAC 202 / 512PAC 2100 / 2200
230 / 70m *750 / 250m7/0.2 0.34mm² 22AWG
230 / 70m *1500 / 500m16/0.2 0.5mm² 20AWG
230 / 70m *3000 / 1000m32/0.2 1.0mm² 18AWG
Notes
These figures (*) are for readers powered from the controller. The cable distances
can be increased to 1650 / 500m by locally powering the readers.
Locally powered readers must be connected to a UL 603 power limited Class 2
supply for US, or a ULC S318 power limited Class 2 supply for Canada.
If you use 22AWG / 0.34mm² cables, twist the wires and double them over before
inserting them in the crimps.
Maximum cable distances will be less for readers which have been set to give
Wiegand output.
Specification
CurrentPowerReader Range
90mA12V–24V DCUp to 4.0 / 100mm
11
English