User's Manual
Usage
LEDs
Red / GreenGreenRed
Access deniedAccess permittedDefault
Sounder
•
The reader sounds 4 rapid beeps when it is powered up or restarted.
•
If specified, the reader beeps once when a token is presented.
Cable Lengths
PAC door controllers only
Distance from Reader to ControllerCable Gauge
PAC 202 / 512PAC 2100 / 2200
230′ / 70m *750′ / 250m7/0.2 0.34mm² 22AWG
230′ / 70m *1500′ / 500m16/0.2 0.5mm² 20AWG
230′ / 70m *3000′ / 1000m32/0.2 1.0mm² 18AWG
Notes
•
These figures (*) are for readers powered from the controller. The cable distances
can be increased to 1650′ / 500m by locally powering the readers.
•
Locally powered readers must be connected to a UL 603 power limited Class 2
supply for US, or a ULC S318 power limited Class 2 supply for Canada.
•
If you use 22AWG / 0.34mm² cables, twist the wires and double them over before
inserting them in the crimps.
•
Maximum cable distances will be less for readers which have been set to give
Wiegand output.
Specification
CurrentPowerReader Range
90mA12V–24V DCUp to 4.0″ / 100mm
11