User's Manual

Reader Tamper
If the backplate is pulled away from the wall, the tamper plate remains attached to the wall
and a wall tamper condition is generated. Likewise, if the reader is removed from the backplate,
a case tamper condition is generated.
The voltage on the Tamper line is normally low. If case tamper or wall tamper is detected, the
voltage on the Tamper line becomes high and the reader sounds 3 long beeps every 5 seconds
for two minutes, then stops.
To clear a wall tamper condition, reattach the backplate to the tamper plate. To clear a case
tamper condition, reattach the reader to the backplate.
Usage
LEDs
YellowRed / GreenGreenRed
Not usedAccess deniedAccess permittedDefault
Sounder
The reader sounds 4 rapid beeps when it is powered up or restarted.
If specified, the reader beeps once when a token is presented.
PIN
Instructions on changing the PIN locally are given in the PAC SecureNet Help file.
Cable Lengths
PAC door controllers only
Distance from Reader to ControllerCable Gauge
PAC 202 / 512PAC 2100 / 2200
230 / 70m *750 / 250m7/0.2 0.34mm² 22AWG
230 / 70m *1500 / 500m16/0.2 0.5mm² 20AWG
230 / 70m *3000 / 1000m32/0.2 1.0mm² 18AWG