Figure 9 Six Wire Bus Wiring
3.1.2 Addresses
The six wire bus works by each door controller having its own unique address. The order in which door
controllers are addressed does not matter nor do they have to be numbered consecutively. Depending on
the type of administration, the following are possible:
Standalone
One master controller (system type 0) address 1 and up to 3 slave controllers (system type 3) addresses
2, 3 and 4.
Up to 32 Door
One master controller (system type 2) address 1 and up to 7 slave controllers (system type 3) addresses
2, 3, 4, 5, 6, 7 and 8.
Single-Site
Up to 32 slave controllers, addresses 1 to 32.
Multi-Site
Via the six wire bus:
Up to 32 slave controllers (system type 3) addresses 1 to 32.
Via the serial link:
Up to 32 sites comprising one master controller (system type 2) address 1 and up to 7 slave
controllers (system type 3) addresses 2, 3, 4, 5, 6, 7 and 8.
Up to 95 sites comprising one slave controller (system type 3).
Notes
1. When being addressed by the CNC, a maximum of 32 controllers can be addressed. When