15263 Ver 2.1 DRAFT E PAC Portico 2200/1200 Series Installation Guide
Page 42 © 2003 Blick USA, Inc.
5.2.1.2 Reader Cabling
Use unshielded, multi-stranded, tinned copper signal cable, the type commonly used in alarm
installations. A minimum of 6-core, 24AWG/0.22mm², cable is required (reader, request to exit and door
contact). It is recommended that 8/12-core cable is used depending on requirements. For example,
some readers have a sounder which require an additional core to make use of the feature.
The maximum reader cable length is dependent on both the reader type and cable gauge as detailed
below. For example, the cable length for the slimline and standard plus readers is:
Up to 750ft/250m 24AWG/ 0.22mm²
Up to 1500ft/500m 20AWG/0.50mm²
Up to 3000ft/1000m 18AWG/1.00mm²
Full details are provided in the documentation supplied with each reader.
Four conductors are used to connect the reader itself, the other conductors can be used for the optional
request to exit and door monitoring signals (see Sections 5.2.2.1 and 5.2.2.2).
The readers are not prone to electrical interference, however avoid routing cable close to heavy load
switching cables and equipment. If this is unavoidable, cross the cable at right angles every 3.3-6.6ft/1-
2m.
5.2.1.3 Reader Connections
Proximity readers have a 6-core flying lead or 4 terminals (+V, VCA, SIG and -V). Each reader is
connected to one of the reader channel terminal blocks on the door controller. Each reader channel has 2
further connections, DC and RTE. These provide door/cable monitoring and request to exit inputs
respectively.
Readers with Terminals
Connects to
Controller
Reader
Marking Description
6-pole
terminal block
screw
terminals
GND -V 0V supply.
SIG1 SIG Signal output. Connect to door controller reader channel SIG.
DC Door monitoring.
RTE Request to exit.
LED VCA Valid code accepted, illuminates the green LED at the reader when
a valid key is presented.
+18V +V 18V supply.
Readers with Flying Leads
Connects to
Controller
Color Signal Description
6-pole terminal
block
GND Black -V 0V supply.
Yellow SNDR Sounder input, active low. Pull to ground to activate
sounder
SIG1 White SIG Signal output. Connect to door controller reader
channel SIG.
- Green Not used
LED Brown VCA Valid code accept, operates LED. Connect to door
controller reader channel, LED.
- Blue Reader tamper connection (not required on the PAC
Portico door controllers)
+18V
Red
+12V
Unregulated 12V dc input 9-28 V dc, 35 mA Max
Orange
+5V
Regulated 5V dc input, 35mA Max
Note
If an entry/exit reader is being used, the SIG from the exit reader connects to the relevant RDRn
connection, see Figure 20.