5.2.2.2 Door Monitoring
The door controller has the ability to monitor a door contact if a door contact is fitted:
Unauthorized Access Alarms giving warning of a forced door.
Door Left Open Warning after a set period of time has expired and the door is still open. The time is
set when the controller is programmed.
Cancellation of Lock Release Time allows the door to lock after someone has passed through even
though the lock release time has not expired.
The door contact should be a normally closed switch that is open whenever the door is open. Care should
be taken when fitting door contacts to ensure that they operate only when the door is opened and close
only when it is secure again.
To help prevent false alarms:
Keep reed switches away from large magnetic fields, such as those generated by magnetic locks.
This is a particular problem with metal door frames.
Ensure that the switch does not operate if the door moves in its frame, in draughty or windy
conditions.
An efficient door closer should be fitted that secures the door once someone has passed through.
5.2.3 In and Out Readers
5.2.3.1 Without Arming
Figure 20 In/Out Readers Without Arming/Disarming
Only one Wiegand reader can be used either as the in or out reader.
If you are using Wiegand readers and require in/out readers, you must use a PAC Portico Wiegand
interface unit for each reader. Call PAC Portico Technical Support for details.