User Manual

15263 Ver 2.1 DRAFT E PAC Portico 2200/1200 Series Installation Guide
Page 60 © 2003 Blick USA, Inc.
7.2.2 M Command - Modem Configuration
At the CMD prompt, type M and press ENT.
ADDRESS 1
Slave Controller Only
Here you set the address of the slave controller, this is only required
when a controller is set to system type 3. All other system types will
have a setting here of 1.
The values available for the address depend on the type of
administration system:
A slave controller as part of a system type 0 (front panel) will have
an address of 2, 3 or 4.
A slave controller as part of a system type 2 (PAC Portico PC
based administration system RS-232 cluster or multi site CNC RS-
232 cluster) will have an address of 2, 3, 4, 5, 6, 7 or 8.
A slave controller connected to a CNC six wire bus will have an
address of 1-32.
Type the address and press ENT.
Press NXT to go on.
BAUD RATE 1200
Available baud rate settings are 300, 600, 1200, 2400, 4800, 9600,
19200.
Depending on the system type the baud rate should be:
Printer attached to front panel administered controller (system type
0): 4800.
Door controller attached to PC interface kit or Direct Master (system
type 2): 9600.
Door controller attached to Single-Site CNC (system type 2): 9600.
Door controller attached to Multi-Site CNC (system type 2 or system
type 3): the baud rate depends on RS-232 devices being used,
modems, line drivers, etc. 300, 600, 1200, 2400, 4800,
9600, 19200.
If a change is required, type the baud rate.
Press ENT then NXT.
CONNECT MODEM N
Type N for no dial-up device connected to the door controller; type Y
for a dial-up device connected to this door controller.
This setting is important as it will ensure that a dial-up device is
correctly programmed to auto-answer. It is also important to ensure that
if no device is connected, this entry is set to N.
Press ENT then NXT.