PAC Portico 2200/1200 Series Installation Guide 15263 Ver 2.1 DRAFT E
© 2003 Blick USA, Inc. Page 61
SETUP RDPHBTX-
To setup remote acknowledge, dialback and comms protection, type
the required numbers (1 to 7). For example, entering 1, 2, 5 and 7
selects those options and displays RD--B-X to show the options
selected. The options are:
R When administered via a PC only.
This indicates whether Remote Acknowledgement is required
for alarms. In this case, if R is showing, a door alarm will only be
cleared at the door controller if it is acknowledged by an operator
at the administration system. This may be the front panel or a
PC. If R is not showing, the alarm will be acknowledged at the
door controller when it is passed to the master controller. This is
important if you use the programmable on-board relays (PC-
based systems only). These relays and those on any attached
alarm module will only be reset when the alarm is accepted by an
operator.
D For use with Multi-Site CNC only. Dialback. In the event of an
alarm condition or Access Authorized (if set up) the door
controller will dial-back to the Multi-Site CNC using the first
number shown in Dialback specification in this section. If it fails
to get through, it will attempt again on the first number. If it fails
again, it will try the second number, if present, twice. This
process will be repeated 5 times. If there is still no success it will
give up, generating a Comms Failed transaction.
P For use with Multi-Site CNC only. Comms Protection. This
setting activates the Comms protection facility.
See the Protect Comms specification in this section.
H For use with Multi-Site CNC only.
Hardware Handshake. Set this if the device being used to
communicate with the CNC requires a hardware handshake
(CTS/DTR). The door controller will not send, or stop sending,
data when its CTS input is low.
See Section 3.3.
B For use with Multi-Site CNC only.
Auto Baud Rate Select. When a modem obtains a connection,
it returns a message stating the baud rate at which it will
communicate. This rate is usually 'negotiated' between modems
when a line is established. When this option is selected, the door
controller will adjust its serial baud rate to match the line speed
See Section 3.3.
T Transaction Restriction. Use this setting only when installing
the PAC Portico 2200/1200 Series Door Controller on a system
such as a PAC Portico 6000 or PAC Portico 2000AM, which
does not recognize transaction types such as Power On, Power
Off, Auto Relay Set etc.
X Not used.
Press ENT then NXT.
Note
It is recommended that the dial-back times are set via a PC.
Type the telephone number 1 for dial-back.
Press ENT then NXT.
Type the telephone number 2 for dial-back.
Press ENT then NXT.