User Manual

Packet Power™ Wireless Smart DC Monitoring System Manual
Copyright 2015 © Packet Power, LLC.
11
Remote Current Transducers: Remote current
transducers are used in applications requiring
higher current sensing or a larger diameter window
than can be provided by the integrated current
sensor or when the conductor cannot be removed
and requires a split core transducer. The remote
current transducers are available in a wide variety
of form factors and current ratings. Consult Packet
Power for a full listing of available remote current
transducers.
Wireless Voltage Monitor Installation
WARNING: Always observe caution working with DC voltage. Failure to do
so can result in death or severe injury. This system is intended for
installation by qualified electrical professionals.
Power for the voltage monitor is sourced directly from the DC bus being monitored so the
monitor must always be connected to the same DC bus it is monitoring. Only one Wireless
Voltage Monitor is needed per DC bus to allow the Gateway to provide power calculations
as the voltage can be shared between any numbers of current monitors on the bus.
Note that if there are significant line voltage drops on the bus being monitored, the Wireless
Voltage Monitor should be placed in a location on the bus where the best representative
voltage can be sourced.
Be sure to use the correct rated Wireless Voltage Monitor for the specified current
range.
Always observe the correct polarity of the connections. Failure to so may result in
permanent damage to the meter.
Connections to the Wireless Voltage Monitor can be made through the two terminals on the
top of the module which are designed to accommodate bare conductor from 12 AWG to 20
AWG. To insert the wiring into push down on the connector tab, insert conductor and
release tab. Always make sure the conductor is secured by giving a slight pull on the cable.
The Wireless Voltage Monitor is internally fused but it is suggested that external overcurrent
protection in the form of an inline fuse with a 0.5A rating be used with the voltage sensing
Remote Current Transducers (CTs)