User Manual

Packet Power Monitoring Module Users Manual
Copyright 2009-2013 Packet Power, LLC.
10
3
Note: If the current transformer(s) are located in the same enclosure as the PMM,
you must ensure that any electrical code fill rate requirements are being met.
LED readings and indicator lights
The PMM has 3 large alpha-numeric LEDs that provide for local display of monitoring
data and 3 small lights adjacent to the LEDs that provide operating status information.
The PMM can be configured to display all or some of the following data via the numeric
LEDs. The order of display can also be customized. The data type indicator is shown
followed by the corresponding value, e.g. to show a reading of 10.1 amps on channel A,
the PMM displays “A1” followed by “10.1”.
P5= XXX firmware version
Id = ABC last 3 digits of the Packet Power node ID
A1 / A2 / A3 = current on channel A, B or C in Amps
U1 / U2 / U3 = voltage on channel A, B or C in Volts
P1 / P2 / P3 = power on channel A, B or C in kilowatts
F1 / F2 / F3 = power factor on channel A, B or C
Fr= frequency in Hz
The 3 status lights are interpreted as follows (top, middle and bottom positions assume
that the PMM is viewed such that the status lights are to the right of the large LEDs):
Top small light (green)
900MHz radio activity
o off: disabled
o solid on: active, not connected
o slow flashing: active, connected to the mesh network
o very rapid flashing: test/configuration mode
Middle small light (red)