Panasonic Submittal

Specification Submittal Data / Panasonic Ventilation Fan
Description
Ventilating fan shall be Low Noise ceiling mount
type rated for continuous run. Fan shall be
ENERGY STAR
®
rated and certified by the
Home Ventilating Institute (HVI). Evaluated by
Underwriters Laboratories and conform to both UL
and cUL safety standards.
Motor/Blower:
• Four–pole totally enclosed condenser motor
rated for continuous run.
• Power Rating shall be 120 volts and 60 Hz.
• Fan shall be UL listed for tub/shower enclosure
when used with a GFCI branch circuit wiring.
• Motor equipped with thermal–cutoff fuse.
• Removable with permanently lubricated plug–in
motor.
Housing:
• Rust proof paint, galvanized steel body.
• 6" diameter duct adaptor.
• Built in backdraft damper.
• Expandable extension bracket up to 26".
Grille:
• Attractive design using PP material.
• Attaches directly to housing with torsion springs.
Warranty:
• ALL Parts: For period of 3 years from the date
of the original purchase.
Architectural Specifications:
Ventilating fan shall be of the ceiling mount, Energy
conserving vent type, with no less than 290
CFM and no more than 2.0 sones as certied by
the Home Ventilating Institute (HVI) at 0.1 static
pressure in inches water gauge (w.g.) and with
no less than 257 CFM as certied by HVI at 0.25
w.g. Power Consumption shall be no greater than
64 watts at 0.1 w.g. and 62 watts at 0.25 w.g.
ENERGY STAR rated with efficiency of no less
than 4.5 CFM/watt at 0.1 w.g. and 4.1 CFM/watt
at 0.25 w.g. The motor shall be totally enclosed,
four pole condenser type engineered to operate
continuously. Power rating shall be120v/60Hz.
Duct diameter shall be no less than 6". Fan shall
be UL and cUL listed for tub/shower enclosure
when used with GFCI branch circuit wiring. Fan
shall be ASHRAE 62.2, LEED, ENERGY STAR IAP,
EarthCraft, California Title-24, and WA Ventilation
Code compliant.
FV-30VQ3
Panasonic Home and Environment Company
Division of Panasonic Corporation of North America
One Panasonic Way
Secaucus, NJ 07094
www.panasonic.com/building
Specications: WhisperCeiling FV-30VQ3
6" Duct
Static Pressure in inches w.g.
0.1 0.25
Air Volume (CFM)
290 257
Noise (sones)
2.0 N/A
Power Consumption (watts)
64 62
Energy Efficiency (CFM/Watt)
4.6 4.1
Speed (RPM)
877 990
Current (amps)
0.53 0.52
ENERGY STAR rated
YES
Washington State VIAQ Code
YES
As of date 4/11
For complete Installation Instructions visit www.panasonic.com/building
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
FV-30VQ3
6" duct
VF11076SS-30
0.00
0.20
0.40
0.60
0.80
1.00
050 100 150 200 250 300 350
Airflow(CFM)
FV-30VQ3
20 Feet
40 Feet
60 Feet
80 Feet
100 Feet
Static Pressure(inch w.g.)