3.1.2 Restriction According to Mounting Directions
If the unit is being installed in a horizontal orientation, or our Programmer II and C-NET adaptor are
being connected to the TOOL port, note that the ambient usage temperature should be as below.
Model
name
Condition
Ambient
temperature
GT11
Vertically installed
0 to 45 °C
Programmer II
C-NET adapter
GT21
Horizontally installed
Programmer II
C-NET adapter
GT32
Horizontally installed
0 to 40 °C
GT03-E
GT32-E
Horizontally installed
-20 to 55 °C
Vertically installed
Note) When installing the unit aslant, the restriction is the same as the one when installing horizontally.
3.1.3 Installation Space
Applicable panel thickness
A panel with a thickness of 1.0 to 5.0 mm should be used.
Use a panel that is strong enough not to be warped.
Clearance when the GT is installed
When installing the GT unit, if other parts are being installed to the panel or cables are being wired to it,
we recommend providing a clearance around the GT unit. This prevents cables from being damaged,
and facilitates the installation work. Also, make sure that the slits in the main unit are never obstructed.
Model name Clearance
Clearance on the surface
to connect the screen
transfer cable
Clearance on the
mounting surface when
using a SD memory card
GT01
GT11
GT21
30 mm or more
(50 mm or more
recommended)
20 mm -
GT02L
GT03M-E
60 mm -
GT02
GT05
GT03T-E
GT12
GT32
GT32-R
GT32-E
60 mm 40 mm or more
* It should be 40 mm or more when using a SD memory card.
3.1.4 UL/c-UL Qualification
Be aware of the following when applying for UL standard for the equipment that the GT has been
built in.
When the GT built in equipment, the GT should meet the standard as a part of the enclosure.
As the rear of the GT is not qualified as an enclosure, provide a fire enclosure (metal barrier) that
entirely covers the rear and lateral sides of the GT.