Datasheet

1
KT
Temperature
Controller
Your Simple, Accurate
and Economical
Temperature Controller
KT4 series
(48
×
48
×
95mm)
KT8 series
(48
×
96
×
98.5mm)
KT9 series
(96
×
96
×
98.5mm)
KT7 series
(22.5
×
75
×
100mm)
FEATURES
1. Multi-input
Versatile thermocouple, RTD, DC voltage
and DC current input for temperature
detecting sensors.
2. Simple operation enables highly
accurate temperature control
All required operations can be enabled by the
front keys and highly accurate PID control
mode ensures an input span of ±0.2%.
3. DIN Rail mounting types are aligned
taking global market demand into
consideration
The KT7 series is equipped with DIN rail
mounting complying to DIN standards.
Furthermore, because its control panel is
compact, the KT7 saves space.
4. Meets market demands for cost-
effectiveness
The KT series offers both economy and
high performance.
5. The KT series complies with UL, CSA
standards and CE marking.
6. Communication specification uses
RS485 and Modbus protocol
* In the configuration above, the FP
requires
a communication cassette (FPG-COM3).
* Modbus is a communication protocol
developed for PLCs by Modicon Inc.
KT4
OFF
MODE
OUT
TX/RX
PV
SV
SV1
SV2
AT
EVT
A1
OUT2
OUT1
KT4
OFF
MODE
OUT
TX/RX
PV
SV
SV1
SV2
AT
EVT
A1
OUT2
OUT1
KT4
OFF
MODE
OUT
TX/RX
PV
SV
SV1
SV2
AT
EVT
A1
OUT2
OUT1
RS-485
Up to 31 units can be connected
FP Programmable Controller
(Matsushita Electric Works)
(Sample System Configuration)
PRODUCT TYPES
1. KT4 Series
Notes: 1. CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
2. Event output will be shared if you choose alarm output 2 and the heater burnout alarm.
• Part No.
(Ex) Part No. when the optional functions (of Heating/Cooling control: SSR output + Communications function) is added on to the basic
model are as follows; Part No.: AKT41111401
• Options
Note: When Current input is specified, a shunt resistor (sold separately) is required.
Base
model
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/
cooling control
Heater
burnout alarm
Communications
function
Description
AKT4 48
×
48
×
95mm
1 100 to 240V AC
2 24V AC/DC
1 Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
1 Relay contact output 1a 3A 250V AC
2 Non-contact voltage output (for SSR drive)
3 Current output
1 Relay contact output 1a (Alarm output 1)
2 Relay contact output 1a (Alarm output 2)
0 Not available
4
SSR output 0.3A 250V AC (Heating/Cooling control not supported when 2
alarm output points are selected)
0 Not available
1
5A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
2
10A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
3
20A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
4
50A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
Not available
1 Available
Product name Part No.
Shunt resistor (for Current input) AKT4810
Terminal cover AKT4801
KT_new.fm1y[WQOOQNPO PVœ@ jœ@ OPP PW“