JPt100 –199.9 to 500.0 : JPt100 –199.9 to 900.0 :
Pt100 –200 to 850 : Pt100 –300 to 1500 :
JPt100 –200 to 500 : JPt100 –300 to 900 :
4 to 20mA –1999 to 9999:
0 to 20mA –1999 to 9999:
0 to 1V –1999 to 9999:
0 to 5V –1999 to 9999:
1 to 5V –1999 to 9999:
0 to 10V –1999 to 9999:
Scaling high limit setting 1370
Sets the scaling high limit value.
Available only for DC input
Scaling low limit value to input range high limit value
(The placement of the decimal point follows the selection.)
Scaling low limit setting –200
Sets the scaling low limit value.
Available only for DC input
Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection.)
Decimal point place selection No decimal point
Selects decimal point place.
Available only for DC input.
No decimal point: 1 digit after decimal point:
2 digits after decimal point: 3 digits after decimal point:
PV filter time constant setting 0.0 seconds
Sets PV filter time constant.
(If the set value is too large, it affects control result due to the delay of response)
0.0 to 10.0 seconds
OUT high limit setting 100%
Sets OUT high limit value.
Not available for ON/OFF action.
OUT low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT low limit setting 0%
Sets OUT low limit value.
Not available for ON/OFF action.
–5% to OUT high limit value
(Setting less than 0% is effective to DC current output type)
OUT ON/OFF action hysteresis setting 1.0
Sets OUT ON/OFF action Hysteresis.
Available only when the control action is ON/OFF action
Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)
Alarm type selection No alarm action
Selects an alarm type.
No alarm action : Process high alarm :
High limit alarm : Process low alarm :
Low limit alarm : High limit alarm with standby :
High/Low limits alarm : Low limit alarm with standby :
High/Low limit range alarm: High/Low limits alarm w/standby:
Alarm action Energized/Deenergized selection Energized
Selects the alarm action Energized/Deenergized.
Not available if No alarm action is selected during the Alarm type selection.
Energized: Deenergized:
Alarm HOLD function selection Alarm Not Holding
Selects either [Holding] or [Not Holding] of alarm HOLD function.
If alarm HOLD function is set to [Holding], once the alarm functions, alarm output
remains until the power is turned off.
Not available if No alarm action is selected during the Alarm type selection
Alarm Not Holding: Alarm Holding:
Alarm hysteresis setting 1.0
Sets the alarm hysteresis.
Not available if No alarm action is selected during the Alarm type selection
Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)