User Manual
8
JPt100 –199.9 to 500.0 : JPt100 –199.9 to 900.0 :
Pt100 –200 to 850 : Pt100 –300 to 1500 :
JPt100 –200 to 500 : JPt100 –300 to 900 :
4 to 20mA –1999 to 9999:
0 to 20mA –1999 to 9999:
0 to 1V –1999 to 9999:
0 to 5V –1999 to 9999:
1 to 5V –1999 to 9999:
0 to 10V –1999 to 9999:
Scaling high limit setting 1370
• Sets the scaling high limit value.
• Available only for DC input
• Scaling low limit value to input range high limit value
(The placement of the decimal point follows the selection.)
Scaling low limit setting –200
• Sets the scaling low limit value.
• Available only for DC input
• Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection.)
Decimal point place selection No decimal point
• Selects decimal point place.
• Available only for DC input.
• No decimal point: 1 digit after decimal point:
2 digits after decimal point: 3 digits after decimal point:
PV filter time constant setting 0.0 seconds
• Sets PV filter time constant.
(If the set value is too large, it affects control result due to the delay of response)
• 0.0 to 10.0 seconds
OUT high limit setting 100%
• Sets OUT high limit value.
• Not available for ON/OFF action.
• OUT low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT low limit setting 0%
• Sets OUT low limit value.
• Not available for ON/OFF action.
• –5% to OUT high limit value
(Setting less than 0% is effective to DC current output type)
OUT ON/OFF action hysteresis setting 1.0
• Sets OUT ON/OFF action Hysteresis.
• Available only when the control action is ON/OFF action
• Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)
Alarm type selection No alarm action
• Selects an alarm type.
No alarm action : Process high alarm :
High limit alarm : Process low alarm :
Low limit alarm : High limit alarm with standby :
High/Low limits alarm : Low limit alarm with standby :
High/Low limit range alarm: High/Low limits alarm w/standby:
Alarm action Energized/Deenergized selection Energized
• Selects the alarm action Energized/Deenergized.
• Not available if No alarm action is selected during the Alarm type selection.
• Energized: Deenergized:
Alarm HOLD function selection Alarm Not Holding
• Selects either [Holding] or [Not Holding] of alarm HOLD function.
If alarm HOLD function is set to [Holding], once the alarm functions, alarm output
remains until the power is turned off.
• Not available if No alarm action is selected during the Alarm type selection
• Alarm Not Holding: Alarm Holding:
Alarm hysteresis setting 1.0
• Sets the alarm hysteresis.
• Not available if No alarm action is selected during the Alarm type selection
• Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)