Datasheet

KT (AKT2,4,7,8,9,4H,4B)
8
COMMUNICATION FUNCTION OVERVIEW
Note: That main setting No. 2 will not be possible on the KT8 and KT9 when the communications functions is added.
PARTS AND FUNCTIONS
1. KT2 series
Item
Specification
KT2, 4, 8, 9, 7 KT4H/4B
Communication type Half-duplex
Communication speed Select 2400, 4800, 9600, or 19200 bps using key operation.
Synchronization type Asynchronous
Protocol Modbus Modbus RTU, Modbus ASCII, MEWTOCOL (Slave)
Coding ASCII Binary/ASCII
Error correcting Command re-send
Error detection Parity check, check sum
Data structure Start bit: 1, Data bit: 7, Parity: Even parity, Stop bit: 1
Interface EIA RS485 compliant
No. of nodes 31
Maximum cable length 1,000 m (cable resistance must be within 50)
PV/SV display (red): Indicates the input value and setting value. During setting mode, characters
and setting value of the setting item are indicated in turn.
MEMO/STEP display (green): Indicates memory number during fixed value control. Indicates step number
during program control.
PV indicator (red): Lights up when the input value (PV) is indicated.
SV indicator (green): Lights up when main setting value (SV) is indicated.
AT indicator (yellow): Flashes during AT (auto-tuning).
T/R indicator (yellow): Flashes during serial communication (Lit while sending data, Unlit while
receiving data)
OUT indicator (green): Lights up when control output or OUT1 (Heating side, option Heating/Cooling
control) is ON. (For DC current output type, it flashes corresponding to the
manipulated variable in a 0.25 second cycle)
EV1 indicator (red): Lights up when Event output 1 or OUT2 (Cooling side, option Heating/Cooling
control) is ON.
EV2 indicator (red): Lights up when Event output 2 is ON.
Increase key ( ): Increases the numeric value.
Decrease key ( ): Decreases the numeric value.
Mode key ( ): Selects the setting mode or registers the setting value.
(By pressing the Mode key, the setting value or selected value can be
registered)
OUT/OFF key ( ): The control output OUT/OFF or program control RUN/STOP can be switched.
1
2
3
4
5
6
7
8
9
10
11
12
13
OFF
MODE
OUT
1
2
3456
11 12 13
7
8
9
10