Datasheet

PF (APF)
3
ds_61C16_0000_en_pf: 120510D
2. Specifications
REFERENCE DATA
1. Electrical life
Tested sample: APF30224
Notes: 1. Switch contacts are all on N.O. side.
2. AC 15 and DC 13 comply with IEC-60947-5-1 testing conditions.
Characteristic Item Specifications
Contact
Arrangement 1 Form A 1 Form C
Contact resistance (Initial) Max. 100 mΩ (By voltage drop 6 V DC 1A)
Contact material AgNi type, AgNi type/Au-plated
Rating
Nominal switching capacity (resistive load) 6 A 250 V AC
Max. switching power (resistive load) 1,500 VA
Max. switching voltage 250V AC
Max. switching current 6 A (AC)
Nominal operating power 170 mW (5 to 24 V DC), 217 mW (48 V DC), 175 mW (60 V DC)
Min. switching capacity (Reference value)
*1
*1 This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual
load.
100 mA 5 V DC (without Au-plated), 1 mA 1 V DC (with Au-plated)
Electrical
characteristics
Insulation resistance (Initial)
Min. 1,000MΩ (at 500V DC)
Measurement at same location as “Initial breakdown voltage” section.
Breakdown voltage
(Initial)
Between open contacts 1,000 Vrms for 1 min. (Detection current: 10 mA)
Between contact and coil 4,000 Vrms for 1 min. (Detection current: 10 mA)
Surge breakdown voltage
(Between contact and coil)
*2
*2 Wave is standard shock voltage of ±1.2×50μs according to JEC-212-1981
6,000 V (initial)
Temperature rise (at 20°C 68°F)
Max. 45°C 113°F
(By resistive method, nominal coil voltage applied to the coil; contact carrying current: 6A.)
Operate time (at 20°C 68°F)
Max. 8 ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.)
Release time (at 20°C 68°F)
Max. 4 ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.) (without diode)
Mechanical
characteristics
Shock resistance
Functional
Min. 98 m/s
2
(Half-wave pulse of sine wave: 11 ms;
detection time: 10μs)
Min. 49 m/s
2
(Half-wave pulse of sine wave: 11 ms;
detection time: 10μs)
Destructive Min. 980 m/s
2
(Half-wave pulse of sine wave: 11 ms.)
Vibration resistance
Functional 10 to 55 Hz at double amplitude of 1 mm (Detection time: 10μs.)
Destructive 10 to 55 Hz at double amplitude of 1.5 mm
Expected life
Mechanical Min. 5×10
6
(at 180 cpm)
Electrical
*3
*3 For cycle lifetime, refer to “Cautions for Use 4)” in NOTES (page 5)
N.O.: Min. 5×10
4
(at resistive load,
6 cpm and nominal switching capacity)
N.O.: Min. 5×10
4
, N.C.: Min. 3×10
4
(at resistive load,
6 cpm and nominal switching capacity)
Conditions Conditions for operation, transport and storage
*4
*4 The upper operation ambient temperature limit is the maximum temperature that can satisfy the coil temperature rise value. Refer to “6. Usage, Storage and Transport
Conditions” in AMBIENT ENVIRONMENT section in Relay Technical Information.
Ambient temperature: –40°C to +85°C –40°F to +185°F;
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
Unit weight Approx. 5 g .18 oz
Load type Voltage Current Ambient temperature No. of ops.
Resistive load 250V AC 6 A 85°C 185°F 30,000
Inductive load
AC 15 250V AC 3 A 25°C 77°F 20,000
DC 13 24V DC 2 A 25°C 77°F 6,000
2. Max. switching capacity
Load Limit Curve
3. Coil temperature rise
Tested sample: APF30224
Measured portion: Inside the coil
Ambient temperature: 28°C 82°F
4. Ambient temperature characteristics
Tested sample: APF30224, 6 pcs.
400
300
200
100
10
0.1
1
5
Current [A]
DC resistive load
Voltage [V]
AC resistive load
6A
0A
50
60
70
80
90
40
30
20
10
0
10090 110 120 14
0
130
Coil applied voltage, %V
Temperature rise, °C
5
10
-20
-40 -20
0
0
20
8560
40
-15
-10
-5
15
20
Pick-up voltage
Drop-ou
t
voltage
Ambient
temperatur
e,
°C
Rate of
change, %