M
ulit System Outdoor Submittal Data
CU-3E19RBU-5
Multi System Outdoor Unit
General Data
Power (V/P/Hz) 208/230/1/60
Circuit Ampacity (A) 15
Fuse Size, Max.(A) 30
Compressor DC Twin Rotary (Inverter Driven)
No. Used 1
Output Power (W) 1.30K
Outdoor Unit
Fan Type Propeller
Motor Type DC Motor (8 poles)
Output Power (W) 60
Airflow CFM 1447 Cooling / 1634 Heating
Coil Type Aluminum (Blue Coated)
Fin Type - Pipe Type Corrugated Fin
Rows - F.P.I. 2 - 19
Tube Size (in) 3/8”
Refrigerant R410A
R410a Pre Charge oz 93.2 oz
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 164’
Line Height Difference, Max (ft.) 49.2’
Line Size (in. O.D. Discharge) 1/4” x 3
Line Size (in. O.D. Suction) 3/8” x 3
Pre-charge, tube length @ shipment
98.4’
Dimensions (HxWxD)
Outdoor Unit (Uncrated) (in.) 31-5/16 x 34-15/32 x 12-5/8
Weight (lbs.)
(Outdoor) Net 159 lbs
Performance Data @ AHRI Standard Conditions (208/230V)
High Heat @ 47F 26,000 BTU
Low Heat @ 17F 20,800 BTU
Cooling
Total Capacity (BTU/H) 19,000 (6,100 - 24,800)
Sensible Capacity (BTU/H) 18,000
Latent Capacity (BTU/H) 1,000
SEER 22
Amps (A) 7.4 - 6.7
Max. Amps (A) 15
Power Inputs (KW) 1.51
Max. Inputs (W) 1,510
Outdoor Sound Rating (dB-A) High 50
Heating
Total Capacity (BTU/H) 26,000 (5,500 - 28,400)
HSPF 10.5
Amps (A) 10.1 - 9.1
Power Inputs (KW) 2,060
Outdoor Sound Rating (dB-A) 52
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit#:
Drawing#:
Operating Range
Cooling (Max)
114F DB/78F WB
Cooling (Min) 14F DB/ - WB
Heating (Max) 75.2F DB/64F WB
Heating (Min)
-5F DB/-6.8F WB