CALCULATING AIR CONDITIONER DISTRIBUTION
The Intelligent Controller calculates energy (electricity and gas) distribution ratios utilizing the
accumulated working time (T/S ON/OFF) or the capacity value of the indoor unit.
* T/S: Thermostat
10.1 Calculating simple distribution
Parameters as listed below are used to calculate simple distribution:
A
RHHi: accumulated operation time for indoor unit i (High fan speed)
B
RHi: accumulated operation time for indoor unit i (Medium fan speed)
C
RLi: accumulated operation time for indoor unit i (Low fan speed)
D
SHHi: T/S ON accumulated time for indoor unit i (High fan speed)
E
SHi: T/S ON accumulated time for indoor unit i (Medium fan speed)
F
SLi: T/S ON accumulated time for indoor unit i (Low fan speed)
G
Pi: Capacity of indoor unit i (in kW)
H
k: Weighing factor for power consumptions as T/S ON and OFF
I
aHH: Weighing factor for High fan speed
J
aH: Weighing factor for Medium fan speed
K
aL: Weighing factor for Low fan speed
* Accumulated operation time = T/S ON accumulated time + T/S OFF accumulated time
Index of indoor unit i power/gas consumptions is calculated.
Here, “TEi” and TGi” denotes the power and gas consumption indexes of the indoor unit i,
respectively.
When “Object of power distribution calculation” is “T/S ON + OFF time”:
The power consumption index is calculated using “Accumulated operation time” and “T/S ON
accumulated time”; the gas consumption index using “T/S ON accumulated time”
For GHP:
TEi = (RHHi x aHH + RHi x aH + RLi x aL) x Pi Formula 1
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi Formula 2
For PAC:
TEi = { (RHHi x aHH + RHi x aH + RLi x aL) /k +
(SHHi x aHH + SHi x aH + SLi x aL)} x Pi Formula 3
TGi = 0
When “Object of power distribution calculation” is “T/S ON time”:
Both the power and gas consumption indexes are calculated using “T/S ON accumulated
time”.
For GHP:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
For PAC:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = 0
Weighing by wind speed is not carried out for models with their speed set only as High or only as High and low.
Distribution ratios are not calculated when you have chosen not to perform distribution ratio calculations. (See “6.3.2
Setting the date, cut-off date, and distribution ratio calculation method”)