Installation Manual

PRINTED IN MALAYSIA
F615173
ENGLISH
INDOOR UNIT OUTDOOR UNIT
Control Board
Cover (Metal)
Lock
Nuts
Knockout
Holes
Plugs
Connectors
Control
Board
Cover
(Resin)
Side
Panel
Connecting Wires
Particular
Plate
Particular Plate’s
opening holes
No. Accessories part Qty. No. Accessories part Qty.
1
Installation plate
1
5
Remote control holder
1
2
Installation plate fixing
screw
5
6
Remote control holder
fixing screw
2
3
Remote
Control
1
7
Drain elbow
1
4
Battery
2
8
Anti-bacterial filter
1
F615173
1
2
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
If a drain elbow is used, the unit should be placed on
a stand which is taller than 3 cm.
If the unit is used in an area where temperature
falls below 0°C for 2 or 3 days in succession, it is
recommended not to use a drain elbow, for the drain
water freezes and the fan will not rotate.
Hose
Install the hose at an angle so that the water smoothly fl ows out.
Drain elbow
7
128
Wall
Wall
Wall
Installation
plate 1
2 screw
More than 1
More than 1
Measuring
Tape
Indoor unit
241.5 mm
128 mm
234.5 mm
128 mm
Lo
Hi
OPEN
CLOSE
More than
2
50 mm
or more
65 mm
or more
(Left and right are identical)
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Vinyl tape
This illustration is for
explanation purposes only.
The indoor unit will actually
face a different way.
100 mm
or more
1000 mm
or more
100 mm
or more
300 mm
or more
It is advisable to
avoid more than 2
blockage directions.
For better ventilation
& multiple-outdoor
installation, please
consult authorized
dealer/specialist.
Installation plate 1
Sleeve ()
Bushing-Sleeve (
)
Bend the pipe as
closely on the wall as
possible, but be careful
that it doesn’t break.
Saddle (
)
Conduit
(Power supply cord (
))
Attached accessories
Control Board cover
Remote control holder fi xing screws 6
Remote control holder
5
Remote
control
3
Additional drain hose (
)
Gas side piping (
)
Conduit
(Connecting cable)
Putty (
)
(Gum Type Sealer)
Installation parts you
should purchase ()
Vinyl tape (wide) ()
Apply after carrying
out a drainage test.
To carry out the
drainage test,
remove the air fi lters
and pour water into
the heat exchanger.
Liquid side piping (
)
Piping direction Do not bend up
drain hose
(Front side)
Right
Rear
Right bottom
Left
Rear
Left bottom
Left
Example: For E18NKK
If the unit is installed at 12.5 m distance, the quantity of additional refrigerant
should be 50 g .... (12.5-10) m x 20 g/m = 50 g.
Required tools for Installation Works
1 Philips screw driver
2 Level gauge
3 Electric drill, hole core drill (ø70 mm)
4 Hexagonal wrench (4 mm)
5 Spanner
6 Pipe cutter
7 Reamer
8 Knife
9 Gas leak detector
10 Measuring tape
11 Thermometer
12 Megameter
13 Multimeter
14 Torque wrench
18 N•m (1.8 kgf.m)
42 N•m (4.3 kgf.m)
55 N•m (5.6 kgf.m)
65 N•m (6.6 kgf.m)
100 N•m (10.2 kgf.m)
15 Vacuum pump
16 Gauge manifold
Read the following “SAFETY PRECAUTIONS” carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
The items to be followed are classifi ed by the symbols:
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated
in instructions. Please remind the customer to keep the operating instructions for future reference.
SAFETY PRECAUTIONS
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit
and cross over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances.
Poor contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc. mix into refrigeration cycle (piping).
Mixing of air etc will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
For R410A model, use piping, fl are nut and tools which is specifi ed for R410A refrigerant. Using of existing (R22) piping, fl are nut and tools
may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
Thickness or copper pipes used with R410A must be more than 0.8mm. Never use copper pipes thinner than 0.8mm.
It is desirable that the amount of residual oil is less than 40mg/10m.
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will
drop and cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not
enough or a defect is found in electrical work, it will cause electrical shock or fi re.
Do not use spliced wires for indoor / outdoor connection cable. Use the specifi ed indoor / outdoor connection cable, refer to instruction 5 INDOOR/
OUTDOOR UNIT ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on
the terminal. If connection or fi xing is not perfect, it will cause heat-up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical
shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current
Interrupter (ALCI) that has been certifi ed by an NRTL Certifi ed Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if
may cause electrical shock and fi re in case of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and
valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating
and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause
refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fi re.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may
cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Be careful with the liquid refrigerant,
it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner.
Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG12 wires.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
Fix power supply connection to a circuit breaker for permanent connection.
Use NRTL approved fuse or circuit breaker (rating refers to name plate) for permanent connection.
Installation work.
It may need two people to carry out the installation work.
Applicable piping kit
Piping size
Gas Liquid
CZ-3F5, 7BP 3/8" (9.52 mm) 1/4" (6.35 mm)
CZ-4F5, 7, 10BP 1/2" (12.7 mm) 1/4" (6.35 mm)
CZ-52F5, 7, 10BP 5/8" (15.88 mm) 1/4" (6.35 mm)
INDOOR UNIT
OUTDOOR UNIT
Do not install the unit in excessive oil fume areas such as
kitchens, workshops etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near a door.
Ensure the spaces indicated by arrows from the wall, ceiling, fence
or other obstacles.
Recommended installation height for indoor unit shall be at least
2.5 m.
If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
There should not be any animal or plant near the unit which could
be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
Do not place any obstacles near the unit which may cause a short
circuit of the discharged air.
If piping length is over the [piping length for additional gas],
additional refrigerant should be added as shown in the table.
Recommended installation height for outdoor unit should be above
the seasonal snow level.
SELECT THE BEST LOCATION
Model
Horse
Power
(HP)
Piping size
Std.
Length
(m)
Max.
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Piping
Length
for add.
gas (m)
Gas Liquid
E18NKK
2.0HP 1/2"
1/4" 5
15 3 20 20 10
E22NKK
2.25HP 5/8" 15 3 20 20 10
Indoor/Outdoor Unit Installation Diagram
Insulation of piping connections
Attaching the remote control holder to the wall
Model
Dimension
123456
E18NKK, E22NKK 585 mm 82 mm 165 mm 158 mm 169 mm 219 mm
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate left edge to unit’s left side is 3.
From installation plate right edge to unit’s right is 4.
b : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is the
center of the hole. Another method is by putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
CAUTION
When the wall is hollow, please be sure to use
the sleeve for tube assembly to prevent dangers
caused by mice biting the connection cable.
15 mm
Putty or caulking compound
ø70 through hole
Sleeve
for tube
assembly
Approx. 5 - 7 mm
Bushing for tube
assembly
Wall
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm
from the wall.
3
4. Finish by sealing the sleeve with putty or
caulking compound at the fi nal stage.
Indoor Outdoor
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
1. To cut
When properly fl ared, the internal surface of the
are will evenly shine and be of even thickness.
Since the fl are part comes into contact with the
connections, carefully check the fl are nish.
Improper fl aring
Inclined Surface
damaged
Cracked Uneven
thickness
3. To are
Bar
Handle
Core
Yo k e
Clamp handle
Bar
0 – 0.5 mm
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe
CONNECT THE CABLE TO THE INDOOR
UNIT
5
1. The inside and outside connection cable can be connected
without removing the front grille.
2. Unscrew the conduit cover and fi x the conduit connector to
conduit cover with lock nut, then secure it against chassis.
3. Connection cable between indoor unit and outdoor unit should
be UL listed or CSA approved 4 conductor wires minimum
AWG16 in accordance with local electric codes.
Ensure the colour of wires of outdoor unit and terminal number
are the same as the indoor's repectively.
Earth lead wire shall be Yellow/Green (Y/G) in colour and
shall be longer than other lead wires as shown in the fi gure
for electrical safety in case of the slipping.
Wire stripping
5 mm
or more
(gap between
wires)
No loose strand when inserted
Indoor/outdoor
connecting
terminal board
10 ± 1 mm
Terminals on the indoor unit 1 2 3
Colour of wires (connection cable)
Terminals on the outdoor unit 1 2 3
Red arrow mark
Chassis
Conduit
Connector
Conduit
Cover
Lock Nut
Rear Side of Indoor Unit
This equipment must be properly earthed.
CAUTION
Do not turn over the
unit without it’s shock
absorber during pull out
the piping. It may cause
intake grille damage.
CAUTION
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take
the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
Earth Wire
longer than
others
AC wires
for safety
reason
Terminal
Board
Holder
Indoor and
outdoor
connection
cable
WIRE STRIPPING AND CONNECTING REQUIREMENT
Conductor fully
inserted
Conductor over
inserted
Conductor not
fully inserted
ACCEPT PROHIBITED PROHIBITED
CUTTING AND FLARING THE PIPING
Piping
Intake grille
Shock absorber
Piping
INDOOR UNIT INSTALLATION
4
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping
slightly downwards.
Drain hose
Connection
cable
How to pull the piping and drain hose out, in case
of the embedded piping
.
PVC tube
for drain
hose
Indoor unit
72 mm
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection cable
Piping
More than
470 mm
More than
1150 mm
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
PVC tube for
drain hose (VP-20)
More than 700 mm
In case of left piping how to insert
the connection cable and drain hose.
Cable
45°
Drain
hose
Piping
Drain hose
from main unit
(For the right piping, follow the same
procedure)
Sleeve for piping hole
Drain hose
Piping
Connection
cable
More than 1150 mm
1. FOR THE RIGHT REAR PIPING
2. FOR THE RIGHT BOTTOM
PIPING
3. FOR THE EMBEDDED PIPING
marking
PUSH
PUSH
To take out the unit, push the
marking at the bottom
unit, and pull it slightly towards
you to disengage the hooks
from the unit.
Guide
surface
Connection cable
About
70 – 80 mm
Connection cable
Gas side
piping
Liquid side
piping
Drain hose
Cover for the
bottom piping
Tape it with piping in a
position as mentioned in
Fig. below.
Cover for
the right
piping
Piping
Drain hose
Cover for
the left
piping
Cover for the
bottom piping
Cover for the
bottom piping
Tape it with
piping in a position as
mentioned in
Fig. below.
Piping
Drain
hose
Cover
for the
left
piping
1. Press the lower left and
right side of the unit against
the installation plate until
hooks engages with their
slot (sound click).
Installation
plate
Unit’s
hook
Cover for piping
In case of the cover is cut, keep
the cover at the rear of chassis as
shown in the illustration for future
reinstallation.
(Left and 2 bottom covers for piping.)
How to keep the cover
Hook the indoor unit onto the
upper portion of installation
plate. (Engage the indoor unit
with the upper edge of the
installation plate). Ensure the
hooks are properly seated
on the installation plate by
moving it in left and right.
Drain hose
Sleeve for
piping hole
Indoor unit
Hooks at
installation
plate
Piping
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Secure the Indoor Unit
Step-4
Insert the connection cable
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Insert the connection cable
Step-4
Secure the Indoor Unit
Step-1
Replace the drain hose
Step-2
Bend the embedded piping
Use a spring bender or
equivalent to bend the piping so
that the piping is not crushed.
Step-3
Pull the connection cable
into Indoor Unit
The inside and outside
connection cable can be
connected without removing the
front grille.
Step-4
Cut and fl are the
embedded piping
When determining the
dimensions of the piping, slide
the unit all the way to the left on
the installation plate.
Refer to the section “Cutting
and fl aring the piping”.
Step-5
Install the Indoor Unit
Step-6
Connect the piping
Please refer to “Connecting
the piping” column in outdoor
unit section. (Below steps are
done after connecting the
outdoor piping and gas-leakage
confi rmation.)
Step-7
Insulate and fi nish the
piping
Please refer to “Piping and
nishing” column of outdoor
section and “Insulation of
piping connection” column as
mentioned in indoor/outdoor
unit installation.
Step-8
Secure the Indoor Unit
(This can be used for left rear piping and bottom piping also.)
Right Rear piping
Right and Right Bottom piping
Install the indoor unit
Secure the Indoor Unit
Insert the connection cable
Replace the drain hose
Use shock absorber
during pull out the
piping to protect the
intake grille from
damage
1
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally with a bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand fi rmly with bolt or nails.
2
INSTALL THE OUTDOOR UNIT
AB
C
D
6
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
PIPING INSULATION
CONNECT THE CABLE TO THE
OUTDOOR UNIT
5
1. Remove control board cover (Resin and Metal).
2. Remove particular plate.
3. Remove plugs
4. Fix the conduit connectors to the knockout holes with lock-nuts, then secure them against the side
panel.
5. All wires pass through conduits & particular plate’s opening hole.
6. Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4
conductor wires minimum AWG16 in accordance with local electric codes.
7. Wire connection to the power supply (208/230V 60Hz) through circuit breaker.
Connect the UL listed or CSA approved wires minimum AWG12 to the terminal board, and connect
the other end of the wires to ELCB / GFCI.
8. Connect the power supply cord and connecting wire between indoor unit and outdoor unit according
to the diagram below.
9. Secure the wire onto the control board with the holder (clamper).
10. After completing wiring connections, reattach the particular plate and control board cover (Metal and
Resin) to the original position with the screws.
11. For wire stripping and connection requirement, refer to instruction 5 of indoor unit.
Earth lead wire shall be Yellow/Green (Y/G) in colour and shall be longer than other lead wires as
shown in the fi gure for electrical safety in case of the slipping.
Model A B C D
E18NKK,
E22NKK
613 mm 131 mm 16 mm 360.5 mm
Holder
Power
supply
cord
Indoor &
outdoor
cable
connection
Terminal
Board
Earth wire
longer than
others
AC wires
for safety
reason
Earth wire
longer than
others
AC wires
for safety
reason
This equipment must be properly earthed.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the
3-way valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 mHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air for approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in
the gauge does not move after approximately fi ve minutes.
Note : BE SURE TO PERFORM THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS
LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR
UNIT AND PIPES in the following procedure.
4
EVACUATION OF THE EQUIPMENT
Please make fl are after inserting fl are nut (locate at joint
portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
Align the center of piping and suffi ciently tighten the
are nut with fi ngers.
Further tighten the fl are nut with torque wrench in
specifi ed torque as stated in the table.
3
CONNECT THE PIPING
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto
the copper pipe.
Align center of piping to valve and then tighten with torque
wrench to the specifi ed torque as stated in the table.
Torque
wrench
Spanner
or Wrench
Do not overtighten, over tightening may cause gas leakage.
Connecting The Piping to Outdoor
Piping size Torque
1/4" (6.35 mm) [18 N•m (1.8 kgf.m)]
3/8" (9.52 mm) [42 N•m (4.3 kgf.m)]
1/2" (12.7 mm) [55 N•m (5.6 kgf.m)]
5/8" (15.88 mm) [65 N•m (6.6 kgf.m)]
3/4" (19.05 mm) [100 N•m (10.2 kgf.m)]
Connecting The Piping to Indoor
Open front panel and remove air fi lters.
(Drainage checking can be carried out without removing the
front grille.)
Pour a glass of water into the drain tray-styrofoam.
Ensure that water fl ows out from drain hose of the indoor unit.
Operate the unit at cooling/heating operation mode for
fteen minutes or more.
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and
the discharge is more than 8°C during Cooling operation
or more than 14°C during Heating operation.
Discharge air
Drain
tray-
styrofoam
1. Open the front panel.
2. Remove the air fi lters.
3. Put the Anti-bacterial fi lter into place as shown in illustration at
right.
Anti-bacterial fi lter 8
Air fi lter
1
3
2
INSTALLATION OF ANTI-BACTERIAL FILTER
EVALUATION OF THE PERFORMANCE
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
CHECK THE DRAINAGE
CHECK ITEMS
Please follow the steps below to take out front grille if necessary such as when
servicing.
1. Set the vertical airfl ow direction louvers to the horizontal position.
2. Slide down the 2 caps on the front grille as shown in the illustration at right,
and then remove the 2 mounting screws.
3. Pull the lower section of the front grille towards you to remove the front grille.
Cap
Vane
Front grille
Cap
Screw
(Move the vane
to upward)
Vane
When reinstalling the front grille, fi rst set
the vertical airfl ow direction louver to the
horizontal position and then carry out
above steps 2 - 3 in the reverse order.
HOW TO TAKE OUT FRONT GRILLE
AUTO SWITCH OPERATION
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is
pressed and release before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed
continuously for more than 5 sec. to below 8 sec..
A “pep” sound will occur at the fi fth sec., in order to identify the starting of Test
Run operation.
3. HEATING TRIAL OPERATION
Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. and release when a
“pep pep” sound is occured at eight sec. (However, a “pep” sound is heard at fi fth sec..) then press
Remote controller “A/C Reset” button once. Remote controller signal will activate operation force
heating mode.
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be changed by the following steps:
a) Press “AUTO” switch continuously for more than 16 sec. to below 21 sec..
A “pep”, “pep”, “pep”, “pep” sound will occur at the sixteenth sec..
b) Press the “A/C Reset” button once. Remote controller signal will activate the Remote controller
sound setting mode.
c) Press the “AUTO” switch once to select Remote controller receiving sound ON/OFF. A “pep”
sound indicates receiving sound ON, and a “pep” sound indicates receiving sound OFF.
Is there any gas leakage at fl are nut
connections?
Has the heat insulation been carried out at fl are
nut connection?
Is the connection cable being fi xed to terminal
board fi rmly?
Is the connection cable being clamped fi rmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the
installation plate?
Is the power supply voltage complied with rated
value?
Is there any abnormal sound?
Is the cooling/heating operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the Anti-bacterial fi lter installed?
Terminals on the indoor unit
Colour of wires (connection cable)
Terminals on the outdoor unit
(power supply cord)
1 2 3
L1 L2 1 2 3
POWER SUPPLY

Summary of content (1 pages)