Dimensions Guide
Specification Submittal Data / Panasonic Ventilation Fan
Description:
Ventilating fan shall be Low Noise ceiling or wall
mount type rated for continuous run. Fan shall
be ENERGY STAR
®
rated and certified by the
Home Ventilation Institute (HVI). Evaluated by
Underwriters Laboratories and conform to both
UL and cUL safety standards.
Motor/Blower:
• Enclosed brushless ECM motor technology
rated for continuous run.
• Fan ventilation rates shall be manually
adjustable for 80 or 100 CFM.
• Power rating shall be 120 volts and 60 Hz.
• Fan shall be UL and cUL listed for tub/shower
enclosure when GFCI protected and used in
insulated ceiling (TYPE I.C.).
• PCB board equipped with thermal–cutoff fuse.
• Removable with permanently lubricated plug-
in motor.
Housing:
• 26 gauge galvanized steel body.
• Built-in 4" Oval duct collar. Also compatible
with 4" round duct.
• Optional 24 gauge steel, fire code rated
4" oval to 3" round duct adaptor sold
separately (Model # FV-VS43R).
• Built in backdraft damper.
• Built-in metal flange provides blocking for
penetrations through drywall as an Air Barrier,
and assists with the decrease in leakage in the
Building Envelope during blower door testing.
• Unique L-shaped bracket simplifies installation
and provides strong support.
Ceiling Radiation Damper:
• WhisperValue DC is UL listed for use with the
Panasonic Ceiling Radiation Damper (Model #:
PC-RD05C5, sold separately).
Grille:
• Attractive design using Poly Pro material.
• Attaches directly to housing with torsion
springs.
Warranty:
• ECM Motor: 6 Years from original purchase
date.
• ALL Parts: 3 Years from original purchase
date.
Architectural Specifications:
Ventilation fan shall be UL and cUL listed
for ceiling or wall mount and tub/shower
enclosure when GFCI protected. Fan shall also
be ENERGY STAR
®
certified with multispeed
control (0, 30-70 CFM, in 10 CFM increments)
that shall be built-in and activated by a wall
switch. Fan shall also incorporate a built-in
speed selector. Choose from 80 or 100 CFM
and no more than 0.4/0.9 sone as certified
by the Home Ventilating Institute (HVI) at 0.1
static pressure in inches water gauge (w.g.)
with no less than 81/101 CFM and no more
than 0.8/1.3 sone as certified by HVI at 0.25
w.g. Power Consumption shall be no greater
than 8.5/12.4 watts at 0.1 w.g. and 13.2/18.0
watts at 0.25 w.g., with efficiency of no less
than 10.0/8.2 CFM/watt at 0.1 w.g. and 6.5/5.7
CFM/watt at 0.25 w.g. The motor shall be
totally enclosed with a brushless ECM motor
engineered to run continuously. ECM motor
speed shall automatically increase when the
fan senses static pressure to maintain selected
CFM. Power rating shall be 120V/60Hz. Duct
diameter shall be no less than 4". Optional
24 gauge steel, fire code rated 4" oval to 3"
round duct adaptor sold separately (Model #
FV-VS43R). Fan can be used to comply with
ASHRAE 62.2, LEED, EarthCraft, California
Title-24 and WA Ventilation Code.
FV-0810VSS1
For complete Installation Instructions visit us.panasonic.com/ventfans
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
FV-0810VSS1
FV-0810VSS1
4″oval duct
4" Oval duct
Performance Curve 4" Oval duct
0.0 0
0.1 0
0.2 0
0.3 0
0.4 0
0.5 0
0.6 0
0.7 0
0.8 0
0 10 20 30 40 50 60 70 80 90 100 110
Static Pressure (inch w.g.)
Airflow (CFM)
FV-0810VSS1
100CFM
80CFM
70CFM
60CFM
50CFM
40CFM
30CFM
4" 20ft duct
4" 40ft duct
4" 60ft duct
4" 80ft duct
4" 100ft duct
Specifications and Additional Features