Product Overview

Specification Data
Panasonic Ventilation Fan
Description
Ventilating fan shall be Low Noise ceiling mount type rated for continuous run.
Fan shall be ENERGY STAR rated and certified by the Home Ventilating
Institute (HVI). Fan shall include energy efficient compact fluorescent lighting.
Evaluated by Underwriters Laboratories and conform to both UL and cUL safe-
ty standards.
Housing:
Rust proof paint, galvanized steel body.
Detachable 4" diameter duct adapter.
Built in backdraft damper.
Double hanger bar system allowing for ideal positioning.
Grille:
Attractive design using PP material.
Attaches directly to housing with torsion springs.
Light:
One 32-watt electronic ballast compact fluorescent lamps included.
One 4-watt, night-light included.
Warranty:
Typical Specifications:
FV-08VKL3 (80 CFM)
Included:
1 Panasonic
32-Watt CFL
Lamp
Panasonic Home & Environment | One Panasonic Way | Secaucus, NJ 07094 | 866-292-7292 | www.panasonic.com/building
For Complete Installation Instructions Visit www.panasonic.com/building
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
As of 1/11
Motor/Blower:
Enclosed DC brushless motor technology rated for continuous run.
Power Rating shall be 120 volts and 60 Hz.
Fan shall be UL listed for tub/shower enclosure when used with
a GFCI branch circuit wiring and use in insulated ceiling (TYPE I.C.).
Motor equipped with thermal cut-off fuse control.
Removable with permanently lubricated plug–in motor.
The factory warranty shall be a minimum of 6 years limited warranty on
the motor and 3 years on the parts
WhisperGreen
Static Pressure in inches w.g. 0.1 0.25
Air Volume (CFM) 80 79
Noise (sones) <0.3 0.6
Power Consumption (watts) 7.4 12.4
Energy Efficiency (CFM/Watt)2 11.2 6.6
Speed (RPM) 866 1166
Current (amps) 0.01 0.02
Washington VIAQ Code
FV-08VKL3
Yes
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0 20 40 60 80 100
A irflow (C FM )
S tatic P ressure (inch w .g.)
FV-08VKL3
20 Feet
40 Feet
60 Feet
80 Feet
100 Feet
FCC Part 18 compliant.
Ventilating fan shall be ceiling mount type, ENERGY STAR rated with no less than
80 CFM and no more than 0.3 sone as certified by the Home Ventilating Institute
(HVI) at 0.1 static pressure in inches water gauge. Power consumption shall be no
greater than 7.4 watts and ENERGY STAR rated with efficiency rating of no less
than 11.2 CFM/watt. The motor shall be enclosed with brushless DC motor
engineered to run continuously. Power rating shall be 120v/60Hz. Duct diameter
shall be no less than 4”. Fan shall be UL and cUL listed for tub/shower enclosure
when used with GFCI branch circuit wiring. Fan shall be UL listed for use in insulated
ceiling (TYPE I.C.) Lamps shall be compact fluorescent utilizing no less than one
32-Watt energy efficient, electronic ballast light bulbs and include one 4-Watt night-
light. Fan shall be California Title 24 compliant.

Summary of content (1 pages)