Submittal Sheet

/ Panasonic ERV
FV-10VEC2
Cold Climate ERV
Panasonic Life Solutions Company of America
IAQ Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
For complete Installation Instructions visit us.panasonic.com/ventfans
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
2 8 -1/ 2
'
8 -7/8 '
2 3 '
4 ' D i a
6 ' D i a
6 ' D i a
4 ' D i a
1 3 '
IAQ19204ST
Canada and is ENERGY STAR
®
FV-10VEC2
Four 4" or 6" ducts
Energy Recovery Ventilator
Optional Exterior Wall Cap (see next page)
DC Motor Technology
r7
Description
Ceiling or wall mount Cold Climate Energy
Recovery Ventilator (ERV) provides a tempered
air supply, humidity control, and a balanced
amount of exhaust to help maintain balanced,
positive or negative pressure throughout the
home. The Panasonic Intelli-Balance ERV is
engineered for use in any North America
climate zone. Version 2 includes new Hi/Lo
Occupant Controlled Boost Capability. Built-in
ASHRAE 62.2 Timing function helps ensure
code compliance.
Motor/Blower:
• ERV shall have Hi/Lo Speed Occupant Controlled
Boost Capability
• Two (2) enclosed DC brushless motors rated
for continuous run.
• ERV Supply and Exhaust ventilation rates
shall be manually adjustable for
50-60-70-80-90-100 CFM.
• Power rating shall be 120 volts and 60 Hz.
• Motor equipped with thermal cut-off fuse control.
• Removable, permanently lubricated, plug–in
motor.
Housing:
• 22 gauge galvanized steel body.
• Four 4" or 6" intake and exhaust ducts.
• Built in dampers on exhaust and Outdoor Air
ducts for defrost and recirculation cycling.
• Filters on supply and exhaust air extend the
life of the ERV core.
• (4) Pressure ports allow for easy airflow
verification.
• Pre-drilled mounting bracket can
accommodate 16", 19", or 24" on center.
Maintenance:
• MERV 8 filter included; MERV 8 (FVFL0810VE1)
and optional MERV 13 (FVFL1310VE1)
replacements available.
• Unobtrusive alarm notifies owner for filter
check and maintenance.
Warranty:
• DC Motors: 6 years from original purchase date
• All Parts: 3 Years from original purchase date.
Architectural Specifications:
ERV shall be ceiling or wall mount type with built-in
speed selectors for both Supply and Exhaust air.
Select from 50/60/70/80/90/100 CFM. ERV shall
have 100 Net CFM on the exhaust ports and 98
Net CFM on the supply ports as tested in
accordance with HVI 915 and 916 standards at 0.1
static pressure in inches water gauge. ERV shall
have 100 Net CFM on the exhaust ports and Net
100 CFM on the supply ports at 0.4" w.g. static
pressure. ERV shall have Hi/Lo Speed Occupant
Controlled Boost Capability. Power consumption
shall be no greater than 81 watts at 0.1" w.g. and
100 watts at 0.4" w.g. static pressure. Apparent
Sensible Effectiveness for heating shall be no less
than 84% at 53 CFM net air flow under 32°F (0°C)
as tested in accordance with CSAC439. Sensible
Recovery Efficiency for heating shall be no less than
64% at 57 CFM net air flow under 13°F (-25°C).
Total Recovery Efficiency for cooling shall be no
less than 60% at 49 CFM net air flow under 95°F
(35°C). The supply port damper shall close when
outdoor temperatures are < -13°F (-25°C) to
prevent freezing of the core. The (2) motors shall be
totally enclosed DC brushless motors rated for
continuous run. DC motor speed shall automatically
increase when the fan senses static pressure to
maintain selected CFM. ERV shall incorporate an
ASHRAE 62.2 Timing function for code
compliance. Power rating shall be 120v/60Hz. Duct
diameters shall be no less than 4". ERV can be
used to comply with ASHRAE 62.2, Ontario,
ENERGY STAR
®
* and Novoclimat requirements;
LEED, IAP, California Title-24, and WA Energy
Code Credits.
ERV Core Technology:
• Indoor and outdoor air passes through
Panasonic’s capillary core technology. This
process tempers supply air while transferring
moisture and energy.
• Built in Frost Prevention Mode prevents the
core from freezing. Frost Prevention Mode
is intuitive and operates without
homeowner intervention.
• Core material permeated with anti-mold
treatment.
When the ERV senses static pressure, its
speed is automatically increased to ensure
that the desired CFM is not compromised.

Summary of content (2 pages)