Specification Data
Panasonic Ventilation Fan
Description
Ventilating fan shall be Low Noise ceiling mount type rated for continuous
run. Fan shall be certified by the Home Ventilating Institute (HVI). Heating
elements shall be included. Evaluated by Underwriters Laboratories and
conform to both UL and cUL safety standards. Fan is not included for
installation over a tub/shower enclosure.
Motor/Blower:
Four–pole totally enclosed condenser motor rated for continuous run.
Power Rating shall be 120 volts and 60 Hz.
Motor equipped with thermal–cutoff fuse.
Removable with permanently lubricated plug–in motor.
Housing:
Rust proof paint, galvanized steel body.
4" diameter duct adapter.
Built-in backdraft damper.
Grille:
Attractive design using ABS.
Attaches directly to housing with torsion springs.
Heater:
Tubular steel sheathed heating element. Nichrome wire with
magnesium oxide for optimal heat transfer and electrical insulation
at elevated temperatures.
90 CFM super quiet, energy efficient blower motor.
Warranty:
The factory warranty shall be a minimum of 3 years
limited warranty on parts.
Typical Specifications:
Ventilating Fan, Heater combination shall be ceiling mount, with no less
than 110 CFM and no more than 0.6 sone as certified by the Home Ventilating
Institute (HVI) at 0.1 static pressure in inches water gauge. Ventilating fan
power consumption shall be no greater than 30.7 watts with efficiency rating
of no less than 3.6 CFM/watt. The motor shall be totally enclosed, four pole
condenser type engineered to run continuously. Power rating shall be 120v/
60Hz. Duct diameter shall be no less than 4”. Fan shall be California Title 24
compliant.
Heating element shall be Nichrome wire in tubular steel sheath construction with
magnesium oxide for optimal heat transfer. Heating element power consumption
no less than 1400 watts. Heating feature shall include a 90 CFM blower fan
with energy efficient condenser type motor and quick 1-minute warm-up.
The heating element is designed to be used for supplemental heating only and
does not contribute to the ENERGY STAR qualification of the product.
Minimum 20 Amp dedicated circuit recommended. For optimum performance,
install heater no more than 8 feet from floor to ceiling.
FV-11VH2 (110 CFM)
For Complete Installation Instructions Visit www.panasonic.com/building
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
Fan Curve FV-11VH2
AIR FLOW (CFM)
STATIC (INCHES OF WATER)
Specifications:
FV-11VH2
Static pressure in inches w.g. 0.1" 0.25"
89011M)FC(emuloVriA
AN6.0)senos(esioN
Power Consumption (Watts) 30.7 30.5
Energy Efficiency: CFM/Watt 3.6 2.9
935778)MPR(deepS
Heating Element (Watts) 1400
52)sttaW(naFretaeH
Fan/Heater (Watts) 1456
Fan/Heater (Amps) 12.2
NoENERGY STAR Rated
Panasonic Home & Environment | One Panasonic Way | Secaucus, NJ 07094 | 866-292-7292 | www.panasonic.com/building
13-5/16”
18-1/8”
14-1/2 or 22-1/2”
4”
16”
7-3/4”
11-1/2”
14-1/2”
DUCT LENGTH
FAN
20 FEET
40 FEET
60 FEET
80 FEET
100 FEET
Quick 1-minute warm-up.