Specification Description

ARCHITECTURAL SPECIFICATIONS PANASONIC
ADVANCED VENTILATION SERIES
REMOTE MOUNTED IN-LINE VENTILATION FAN FOR SINGLE OR MULTIPLE INLETS
FV-40NLF1 WhisperLine Ventilating fan shall be remote mount, energy conserving type, with
no less than 440 CFM at 0.2” static pressure in inches water gauge and no more than 2.1 sones
as rated by manufacturer at 0.2” static pressure. Power consumption shall be no greater than 60
watts and Energy Efficiency rating shall be no less than 3.3 CFM/watt. The motor shall be totally
enclosed, four pole condenser type engineered to run continuously. Power rating shall be
120v/60Hz. Housing shall be insulated to reduce condensation. Duct diameter shall be no less
than 8”. Fan shall be UL and cUL listed for tub/shower enclosure when GFCI protected. Brackets
shall be provided for joist, truss or suspension installations.