User manual

Wiring
3.4 Common Precautions
3.4.1 Wiring of Analog I/O Unit
Wiring diagram
Voltage input Current input
V
COM
I
Analog device
V
COM
I
Analog device
*1
*1: For the current input, short-circuit the V and I terminals.
Voltage output Current output
Analog device Analog device
V
COM
I
V
COM
I
Precautions on Wiring
Use double-core twisted-pair shielded wires. It is recommended to ground the shielding.
However, depending on the conditions of the external noise, it may be better not to ground
the shielding.
Do not have the analog input wiring close to AC wires, power wires, or load wires.
Do not have the analog output wiring close to AC wires, power wires, or load wires.
Compatible cable (twisted wire)
Size Nominal cross section area
AWG#28-16 0.08 mm
2
-1.25 mm
2
Special tools
Manufacturer Serial number (model number)
Phoenix Contact Co. SZS0.4×2.5(1205037)
3-8