User manual

Basic Instructions
2 150
Outline Performs OR operation by comparing two double word data items with
the comparison condition. The contact goes on or off depending on the
result of the comparison. The contacts are connected in parallel.
19
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
Y30
0
D> =, DT 0, DT100
S1 S2
X0
1
0
1
10
ST X 0
ORD> =
DT 0
DT 100
OT Y 30
S1 32-bit equivalent constant or lower 16-bit area of 32-bit data to be compared
S2 32-bit equivalent constant or lower 16-bit area of 32-bit data to be compared
Operands
Operand
Relay Timer/Counter Register
Index
register
Constant
Inde
x
Operand
WX WY WR
WL
(*1)
SV EV DT
LD
(*1)
FL
(*2)
IX
(*3)
IY
(*4)
K H
Index
modifier
S1 A A A A A A A A A A N/A A A A
S2 A A A A A A A A A A N/A A A A
(*1) This cannot be used with the FP0/FPe.
(*2) This cannot be used with the FP0/FP0R/FPe/FPΣ/FPX.
(*3) With the FPΣ,FPX, FP0R, FP2, FP2SH, and FP10SH, this is I0 to IC.
(*4) With the FPΣ,FPX, FP0R, FP2, FP2SH, and FP10SH, this is ID.
ORD =
ORD <>
ORD >
ORD >=
ORD <
ORD <=
32bit data comparison:
OR equal
32bit data comparison:
OR equal not
32bit data comparison:
OR larger
32bit data comparison:
OR equal or larger
32bit data comparison:
OR smaller
32bit data comparison:
OR equal or smaller
A: Available
N/A: Not Available