User manual

Highlevel Instructions
3 137
Outline Compares one 32-bit data item with the data band specified by two
other 32-bit data items and the comparison result is output to the
special internal relay.
For the FP0R/FPΣ/FPX/FP0/FPe, the P type highlevel instruction
“P63 (PDWIN)” is not available.
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
50
F63 DWIN , DT 10 , DT20 , DT30
Trigger
64
67
70
R900A
R900B
R900C
S1
Y10
Y11
Y12
R0
R0
R0
R0
S2
S3
Lower limit value
Upper limit value
50
51
64
65
66
67
68
69
70
71
72
ST R 0
F63 (DWIN)
DT 10
DT 20
DT 30
ST R 0
AN R 900A
OT Y 10
ST R 0
AN R 900B
OT Y 11
ST R 0
AN R 900C
OT Y 12
S1 32-bit equivalent constant or lower 16-bit area of 32-bit data to be compared
S2 32-bit equivalent constant or lower 16-bit area of 32-bit data for lower limit
S3 32-bit equivalent constant or lower 16-bit area of 32-bit data for upper limit
Operands
Operand
Relay Timer/Counter Register
Index
register
Constant
Inde
x
Operand
WX WY WR
WL
(*1)
SV EV DT
LD
(*1)
FL
(*2)
IX
(*3)
IY
(*4)
K H
Index
modifier
S1 A A A A A A A A A A N/A A A A
S2 A A A A A A A A A A N/A A A A
S3 A A A A A A A A A A N/A A A A
(*1) This cannot be used with the FP0 and FPe.
(*2) This cannot be used with the FP0, FPe, FP0R, FPΣ, FPX.
(*3) With the FP0R, FPΣ,FPX, FP2, FP2SH, and FP10SH, this is I0 to IC.
(*4) With the FP0R, FPΣ,FPX, FP2, FP2SH, and FP10SH, this is ID.
F63
P63
(PDWIN)
(DWIN)
32-bit data band comparison
A: Available
N/A: Not Available