21: Autotuning bias value (S4+6)
Autotuning is executed with (set value (SP) autotuning bias value) as a set value (SP’).
It is used to control excessive temperature rise while autotuning is performed.
For the forward operation, autotuning is executed with (set value (SP) + this set value) as a set value.
Temperature
During autotuning
KP, TI and TD calculation
PID control
Autotuning in reverse operation
Time
Set value
(SP)
Autotuning bias value
(SP’)
Autotuning in forward operation
Temperature
KP, TI and TD calculation
PID control
Time
Set value
(SP)
Autotuning bias value
(SP’)
During autotuning
Note) Even if starting autotuning in the condition that measured value (PV) is close to set value (SP),
autotuning is performed with the above SP’.