1. When in Trouble
Protective function (Detail of error code)
Time characteristics of Err16.0 (Overload protection)
Overload protection time characteristics
Time [s]
MSME 50W
MSME 100W100V
MSME 100W200V
MSME 200W
MSME 400W
MSME 750W200V
MSME 750W(400V),
1.0kW to 5.0kW
MDME 400W(400V),
600W(400V),
1.0kW to 15.0kW
MFME 1.5kW to 4.5kW
MHME 1.0kW to 7.5kW
MGME 0.9kW to 6.0kW
* MDME 7.5kW to 15.0kW, MHME 7.5kW and MGME 6.0kW is less than 300%.
* Only for position control type is not provided with MSME 50W to 750W(200V), 750W(400V),
MDME 400W(400V), 600W(400V), 7.5kW to 15.0kW, MFME, MHME 7.5kW and MGME 4.5kW, 6.0kW.
100
115
0.1
1
10
100
200 300 400 500
Torque [%]
Time [s]
100
115
0.1
1
10
100
200 300 400 500
Torque [%]
Motor Type: M * MD
Motor Type: M * ME
MSMD 50W
MSMD 100W100V
MSMD 100W200V
MSMD 200W
MHMD 200W
MSMD 400W
MHMD 400W
MSMD 750W
MHMD 750W
* Only for position control type.
Caution
Use the motor so that actual torque stays in the continuous running range shown in “S-T
characteristic” of the motor. For the S-T characteristics, see P.7-55 Motor characteristics
(S-T characteristics).